6.3.3 PSU Status Page
6.3.4 Config. Page
The "PSU Status" page displays the operating information of each PSU, including output current, internal temperature,
serial number, firmware version, alarm, and status.
On this page, there are Bus voltage, PSU current, clear Event Log/Data Log, Data Log time interval setting, programmable
relay setting, and PSU ON/OFF that can be set and altered.
6.3.4.1 Bus Voltage / PSU Current
If the Bus voltage/PSU current you set is not within the adjustable range, it will become invalid. Make sure the
parameters that you type in are not over or less than the range as below. After settings, click the "Save" button to
save your parameters.
Adjustable range of Bus voltage/ PSU current
, take RCP-2000 for example, please refer to its user's manual.
Note : If the set PSU current exceeds 100A, the maximum rated current, OTP might be triggered after operating
a period of time.
Bus voltage range
10.5 ~ 14V
21 ~ 28V
42 ~ 56V
PSU current (Output Current) range
30 ~ 112A
24 ~ 89.5A
12.62 ~ 47A
Type
12V
24V
48V
Adjustable range