40
Input/ Output
115VAC
230VAC
+12VDC
+24VDC
+48VDC
Other commonly used wires
Module
1
unit
1
unit
1
unit
1
unit
1
unit
2
unit
2
unit
2
unit
3
unit
3
unit
3
unit
Current
16Arms
10Arms
100Adc
80Adc
42Adc
200Adc
160Adc
84Adc
300Adc
240Adc
126Adc
Minimum Cross-section of Copper Wire
14AWG UL1015
18AWG UL1015
22mm
22mm
5.5mm
60mm
50mm
22mm
30mm
125mm
80mm
16AWG UL1015
12AWG UL1015
10AWG UL1015
30mm
50mm
60mm
80mm
100mm
125mm
150mm
200mm
250mm
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Maximum Current
12A
6A
115A
115A
49A
217A
190A
115A
344A
240A
139A
8A
22A
35A
139A
190A
217A
257A
298A
344A
395A
469A
556A
8.2
De-rating
8.3
EMI Suppression Arrangement
8.4
Warranty
◎
EMI radiation test is greatly affected by wiring. Attaching an EMI suppressor (ferrite core) to the AC cable as close as possible
◎
When using a RJ-45 cable as your interface cable, it might be needed to attach an EMI suppressor (ferrite core) to the cable as
close as possible to the Ethernet connector (JK1) to reduce EMI radiation interference. There are TDK ZCAT2032-0930, NEC
ESD-SR-160, and EROCORE FH 28
×
9
×
16 available for that purpose.
to the AC inlet to reduce the noise is recommended. There are suggested components for reducing EMI radiation interference
including TDK HF70RU26*29*13S, NEC ESD-SR-250H, and EROCORE FH29.7*13*25.9.
◎
Three years of global warranty is provided for RCP 2000 series/ RKP-CMU1 under normal operation. Please do not change
any component or modify the unit by yourself or MEAN WELL may reserve the right not to provide the complete warranty
service.
Table 8-1 Suggested wire selection for input/output wirings
Figure 8-2 Output de-rating curves for RCP-2000 series
L
O
A
D (
%
)
INPUT AC VOLTAGE (VAC) 60Hz
90
100
115
180
24V,48V
12V
264
90
100
80
70
75
65
50
40
AMBIENT TEMPERATURE (
℃
)
L
O
A
D (
%
)
230VAC
Input only
-40
-25
0
-10
15
30
50
60
70
20
40
60
50
80
100
(HORIZONTAL)
◎
According to definition of the Rack Power, output over-current protection will de-rate automatically when AC input is low.
Take RCP-2000 as an example as curve below, as Figure 8-2 de-rating.
Содержание RKP-1U-CMU1
Страница 1: ...RKP CMU1 RKP 1U CMU1 Instruction Manual...