25
5.2.4.2 Setting of Clear EventLog/DataLog and DataLog Time Interval
5.2.4.3 Setting of Programmable Relay
The "Set Clear EventLog/DataLog" box is used to clear the data that Event log/Data log has stored, while the "Set
Each relay can be set for the functions below :
1.Alarm activating: Any Alarm, OVP, OLP, OTP, Short circuit, High Temp., AC Fail, Fan lock, or PMBus Error.
2.PSU ON activating: Immediately, or Delay (1~600 sec).
3. PSU OFF activating: Immediately, or Delay (1~600 sec).
4. Digital I/P activating: Control by DI1, control by DI2, control by DI3, or control by DI4.
DataLog time interval" box can set the time interval from 1 to 60 minutes.
5.2.4.1 Bus Voltage / PSU Current
If the Bus voltage/PSU current you set is not within the adjustable range, it will become invalid. Make sure the
parameters that you type in are not over or less than the range as below.
Adjustable range of Bus voltage/ PSU current
, take RCP-2000 for example, please refer to its user's manual.
Note : If the set PSU current exceeds 100A, the maximum rated current, OTP might be triggered after operating
a period of time.
O n c e y o u i n s e r t t h e c o r r e c t u s e r n a m e a n d p a s s w o r d , y o u w i l l e n t e r t h e s e t t i n g s p a g e . O n t h i s p a g e , t h e r e a r e B u s
voltage, PSU over-current, clear Event Log/Data Log, Data Log time interval setting, programmable relay setting, and PSU
ON/OFF that can be set and altered.
Model
Bus voltage range
PSU current range
12V
10.5 ~ 14V
30 ~ 112A
24V
21 ~ 28V
24 ~ 89.5A
48V
42 ~ 56V
12.62 ~ 47A
Adjustable
Range
Click the scroll-down list of the "Function"
to select an activation group