39
8.1.2
RKP-1U -CMU1 Arrangement
◎
Mount the rack unit in a 19" rack before operating.
◎
Insert 1~2 units of RCP-2000 with the identical output voltage and current into the rack unit. Refer to Figure 8-1.
◎
Assign their addresses through the 5-pole Address Switches (refer to Table 3-5). Definition of the module position: A is in
the middle and B is on the left.
◎
This unit is equipped with built-in DC fans and requires clearance for cooling. There should be no barriers within 10cm of
the ventilation holes.
◎
Connet the AC inputs of A and B units to AC source.
◎
Recommended input/output wires are in Table 8-1.
◎
Wire up your interface cable (USB/RS232), programmable relays, and digital input signals, depending on your application.
◎
Apply a 12~15 VDC to the SK100 port on the rear of the RKP-CMU1 in order to power on RKP-CMU1.
Figure 8-1 System assembly diagram of RCP series
8.2
8.2
Mounting Bracket
Fig1
Fig3
Air flow
direction
1
14
13
25
22
5
0
1
2
5
1
2
5
22
5
0
1
2
5
1
2
5
3
5
0
.8
2
4
3-M5 L=6mm
3-M5 L=6mm
10.2
4
4
7
.1
7
466.1
Module B
Module A
483.6
440
SVR1
SVR1
2
9
.4
8
7
.4
2
ADDRESS
ADDRESS
ADDRESS
ADDRESS
SWITCH
SWITCH
IEC320-C20
IEC320-C20
SWITCH
SWITCH
RKP-1UT-CMU1
RKP-1UI-CMU1
10
10
DC OK
DC OK
46
JK
1
JK
1
DC
DC
IN
IN
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Eth
ern
et
Eth
ern
et
RS
-2
32
RS
-2
32
RY1
RY1
RY2
RY2
RY3
RY3
RY4
RY4
1
1
14
14
13
13
25
25
A
A
B
B
+
+
_
_
8
1
1
8
JK500
JK500
TB4
TB4
SK100
SK100
CN500
CN500
CN502
CN502
CN503
CN503
2
1
Fig2
N
N
FG
FG
N
L
L
8
8
1
1
M E A N W E L L
Frame Ground
AC Input (B)
AC Input (A)
DC Output
DC Output
AC Input (B)
AC Input (A)
1 2 3 4 5
ON
JK1
Содержание RKP-1U-CMU1
Страница 1: ...RKP CMU1 RKP 1U CMU1 Instruction Manual...