Technical Manual
Blind Push Button Smart 55
BE-JTA5504.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
54
54
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Request logic objects after
reset
not active
active
Setting whether the logic objects are to
be automatically requested after
restarting the unit.
Setting Logic A - H
not active
AND
OR
XOR
Setting the logical operation
Object type for logic
output
switch
scene
value
percent value
Setting the object type for the output
object
Sending condition
not automatic
input telegram
change of output
change of output only
value 1
change of output only
value 0
Setting when the value of the output is
sent.
Only available with object type for
logic output "switch".
Invert output
no
yes
Reverses the output when activated
(0
1, 1
0)
Only available with object type for
logic output "switch".
Scene number
1 – 64
[2]
Setting which scene is sent when the
logic function is fulfilled.
Only for the output object type
"scene".
1Byte Value
0 – 255
[0]
Setting which value is sent when the
logic function is fulfilled.
Only for the output object type
"value".
Percent value
0% – 100%
[0%]
Setting which percentage value is sent
when the logic function is fulfilled.
Only for the output object type
"percent value".
Input logic 1 – 4
not active
active normal
active inverted
Setting how an input is to be included in
the evaluation
Table 36: Settings – Logic A-H