46
Switching times in the device:
will be transmitted:
The parameter block is transmitted depending on the parameter
"Setting the time switch"..
remain unchanged:
The memory block for the switching times is not written by the ETS and
the parameter "Setting the time switch" is hidden.
Setting the time switch:
fix via database
: The switching times can only be set in the database and cannot be changed
in the unit.
manual input and database (database overwrites all switching times)):
The switching times
can be set in the database and the unit. With each transmission, the complete values are
written from the database to the unit.
manual input and database (Transmission aborted if switching times are changed on the
device)
: Before the transfer, the ETS makes a comparison between the switching times set in
the database and those in the device. If these are not the same, the download is aborted.
Attention: With this selection, the application must be fully programmed. Partial
programming is not sufficient.
Make up switching times:
The make-up of the switching times allows you to set whether switching states that were omitted
due to unscheduled events are made up.
Make up switching times on restart
After a restart, the last switching statuses are caught up, i.e. the time switch restores the
status that should be in effect at that time.
Make up switching times on time change
In the case of a time jump forward, i.e. a time adju..min/h, the switching events that
were omitted due to the time jump are made up. In the case of a time jump up to +90min, all
switching events are made up. From a time jump of 90min only the last per function.
Make up switching times after unlock
After unlocking, the switching statuses that were omitted during unlocking are restored. This
ensures that all systems are in the "correct" state after unlocking.
Public holiday function
The unit has a comprehensive logic integrated to be able to calculate public holidays. This calculation
can be activated via the parameter "
automatic calculation of public holidays
". A new menu then
appears. See
4.5.2 Automatic calculation of public holidays
In addition, public holidays can be activated manually via object 30 if the parameter "
Manual control
via object
" is set to active. There is also an automatic reset function for this parameter. If the public
holiday is deleted, for example, on the 1st day change, the function can be used for the current day,
as the public holiday then ends for the unit at 00:00.
If, for example, the raising of the shutters in the morning is to be prevented on the next day, the
reset may only take place on the 2nd day change, since in this case a "
public holiday
" is sent to the
object the evening before. In this case, the automatic reset takes place on the following day at 00:00.