4.5.2 PI control continuous
The following settings are available at the ETS-Software (here for controller type heating):
Figure 18: PI control continuous
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
[default value]
comment
Direction of controller
normal
inverted
indicates the controlling behavior at
rising temperature (4.5.5)
Max value of control
value
100%; 90%; 80%; 75%; 70%; 60%; 50%;
40%; 30%; 25%; 20%; 10%; 0%
[100%]
indicates the output power at maximum
amount
Heating system
Warm water heating (5K/150
min)
Underfloor heating (5K/240 min)
Split Unit (4K/90min)
Adjustment via control
parameter
Adjustment of the used heating system
Individual parameterization available by
Adjust e t ia o t ol pa a ete
Cooling system
Split Unit (4K/90min)
Cooling ceiling (5K/240 min)
Adjustment via control
parameter
Adjustment of the used cooling system
Individual parameterization available by
Adjust e t ia o t ol pa a ete
Proportional range (K)
1K-8K
[2K]
By choosing heating/cooling system as
Adjust e t ia o t ol pa a ete , the
proportional range can be
parameterized freely
Reset time (min)
15min
–
210 min
[150 min]
By choosing heating/cooling system as
Adjust e t ia o t ol pa a ete , the
reset time can be parameterized freely
Send control value cyclic
Disable, 1 min, 2min, 3min, 4 min,
5min, 10min, 15min, 20min, 30min,
40min, 50min, 60min
[Disable]
Activation of cyclic sending of the
control value with adjustment of the
cyclic time
Use additional level
No
Yes
Activation of an additional level
available, only for heating (4.5.6)
Table 35: PI control continuous