Technical Manual Temperature Controller
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
27
The DPT RHCC Status object is an additional 2 Byte status object with additional status messages. If
more than one testify is valid, also here the values will be added in the same way as at the HVAC
object.
The following chart shows the hex values for the single messages:
Bit
DPT RHCC Status
Hex-Value
0
Error Sensor
1=Error
0x01
8
Heating/Cooling
0=Cooling/1=Heating
0x100
13
Frost alarm
1=Frost alarm
0x2000
14
Heat alarm
1=Heat alarm
0x4000
Table 21: Hex-Values DPT RHCC Status
The Controller reacts always to the value, which was sent last. If you switched the operating mode
last via 1 Bit, the controller will react to the changeover by 1 Bit. If you switched the operating mode
last via 1 Byte, the controller will react to the changeover by 1 Byte.
The communication objects for the mode selection are shown at the following chart. The first 3
communication objects are for the 1 Bit changeover, the last 3 objects are for the changeover via 1
Byte:
Number
Name
Length
Usage
10
Mode Comfort
1 Bit
Activation of the mode comfort
11
Mode Night
1 Bit
Activation of the mode night
12
Mode Frost/Heat protection
1 Bit
Activation of the mode Frost/ Heat protection
22
DPT_HVAC Status
1 Byte
Visualization of the chosen operating mode
25
DPT_RHCC Status
2 Byte
Visualization measuring/ status of the controller
26
mode selection
1 Byte
Selection of the operating mode
Table 22: Communication objects for the operating mode changeover