Technisches Handbuch Bewegungsmelder SCN-BWM55.x1
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
34
34
Follow-up time
1s-4h
[5min]
Setting the follow-up time
Locking or enabling
object
Lock object universal
Enabling object
Setting whether a locking or enabling
object is to be used
Separate switch object
at night
not active
active
Displays a separate object for night
mode
Output object sends at
only On
On and Off
Output filter for the first output object
Output object sends
cyclic
not active
10s-60min
Activation of cyclic sending for the first
output object
Table 14: Settings - Alarm function
The alarm function can be used to monitor a room in case of absence and to call certain actions in
the KNX system during motion detection.
The individual parameters are described in more detail below:
Release sensitivity for Day/Night
The release sensitivity describes the sensitivity in stand-by mode (the output is switched off, no
motion has been detected)
Presence sensitivity
Presence sensitivity describes the sensitivity in presence mode (the output is switched on, a motion
has been detected.).
Motion filter in Standby
In order to avoid false detection, a motion filter can be activated which filters out very short motions
e. g. by draughts.
Follow-up time
The follow-up time describes the time that expires after the last detection of a motion until the
output is switched off. For example, with a follow-up time of 3 minutes, the light would be switched
on for at least 3 minutes with motion detection. Each new detection leads to a retriggering and thus
to a restart of the follow-up time..
Locking or enabling object
To lock or enable the alarm channel, you can activate a lock or enabling object. The lock object
switches off the channel with a 1, the enable object activates the alarm channel with a 1..
Separate switch object at night
This parameter displays a separate switch object for night mode..
Output object sends at
This parameter can be used to activate a sending filter for the output. If you want the output to send
only ON commands, you have to use the setting "only ON".
Output object sends cyclic
Activation of cyclic sending for object 50 "Alarm - output 1".