By activating "Lock object ON", the light channel sends the output value ON and remains in the ON
state until the locking process is deactivated..
The following table shows the corresponding communication objects:
Number
Name
Length
Usage
6
Lock object
1 Bit
Locking the light channel
6
Force control object
2 Bit
Activate/deactivate force control
7
Lock object ON
1 Bit
Switching on the light channel and locking the
light channel in the ON state
Table 7: Communication objects - Force control/lock object
4.2.5 Output object
The following figure shows the settings for the output object:
Figure 7: Settings - Output object
The following table shows the possible settings for these parameters:
ETS-Text
Dynamic range
[default value]
Comment
Object type for output
–
light
Switching
Dimming absolute
Scene
Selection of the output object to be
triggered with the light channel
Table 8: Settings - Output object
The parameter "Object type for output" defines the data point type of the output object.
Output object: Switching
If the object type "Switching" is selected, a separate object for night operation can be displayed. For
example, the main light can be switched on during daytime operation and a small orientation light
can be switched on during night time operation.
The following table shows the general communication objects:
Number
Name
Length
Usage
0
Light channel 1
–
Output 1
(day)
1 Bit
Switching function of the light channel for
daytime operation
1
Light channel 1
–
Output 1
(night)
1 Bit
Switching function of the light channel for night
operation
2
Light channel 1
–
Output 2
1 Bit
Second switching function of the light channel
Table 9: Communication objects - Output object "switching"