4.2.3 Follow-up time
The following figure shows the available settings for the follow-up time:
Figure 5: Follow-up time
The delay time describes the time that expires after the last detection of a movement until the
output is switched off. For example, with a follow-up time of 3 minutes, the light would be switched
on for at least 3 minutes with motion detection. Each new detection leads to a retriggering and thus
to a restart of the follow-up time..
In addition, a "reduction of follow-up time" can be activated. In this case, two additional parameters
are displayed:
Maximum duration for short time presence:
Indicates the duration between the first and last
motion detection to activate the short-time presence..
Follow-up time for short time presence:
Indicates the duration of the follow-up time if the short-
time presence has been activated.
If the first and last movement within the set duration for short-time presence was detected when
short-time presence was activated, the output is not switched on for the regular follow-up time, but
only for the follow-up time of the short-time presence.