Technical Manual Motion Detector SCN-BWM55.x1
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
Objects per HCV:
40
HCV - Output 1
Dimming absolute
Switching
Scene
DPT 5.001
DPT 1.001
DPT 17.001
send
HCV channel sends
output telegram
Switch actuator /
Dimming actuator/
Heating actuator
Data point type depends on the
parameter "Object type for
output
–
climate (HCV)". Object
sends values according to the
set parameters.
43
HCV - Input
External push button
short
DPT 1.001
receive
HCV channel
reacts to incoming
telegram
External push
button
The object is permanently
displayed and is used to
override the automatic control
of the HCV channel.
44
HCV - Input
External push button
long
DPT 1.001
receive
HCV channel
reacts to incoming
telegram
External push
button
The object is permanently
displayed and is used for
overriding the automatic
control of the HCV channel.
45
HCV - Input
External Motion
DPT 1.001
receive
HCV channel
reacts to incoming
telegram
Additional motion
detector
configured as slave
Object is permanently
displayed and is required for
the Master/Slave function
46
HCV - Input
Force control/
Lock object
DPT 2.001/
DPT 1.003
receive
HCV channel
reacts to lock
command / Force
control
External push
button for
blocking/overriding
the motion
detector
Object is displayed after
activation; DPT depends on
parameter settings
47
HCV - Input
Lock object ON
DPT 1.003
receive
HCV channel
reacts to lock
command
External push-
button for blocking
the motion
detector
Object is displayed after
activation