Technisches Handbuch Bewegungsmelder SCN-BWM55.x1
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
28
28
4.2.7 Process Diagram
Fully automatic without orientation light:
Figure 10: Process diagram - Fully automatic without orientation light
In the operating mode "Fully automatic", the motion detector switches on automatically when
movement is detected. The object "External push button short" can be used to override the
automatic mode of the motion detector and force the motion detector into manual mode. From this
mode, the detector automatically returns to auto mode according to the settings in the menu
"General settings" - "Release of push button input"
If the output of the light channel is switched on (automatic mode - ON or manual mode - ON) and the
light channel is switched off via the object "External push button short", then the light channel is
blocked for 10 seconds for motion detection in order to leave the room and prevent brief restart.