4.7 Temperature measurement
Important
: This function is only available for push-buttons with temperature sensor!
Using the internal temperature sensor, the actual temperature of the room can be recorded and
output to the bus.
The following picture shows the menu for temperature measurement:
Figure 52: Settings
–
Temperature measurement
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Temperature
measurement
▪
not active
▪
active
Activation of the temperature
measurement.
Send measured value
on change of
…
not active, 0.1 °C
–
5.0 °C
[0.2 °C]
Setting whether and at which change
the measured value is to be sent.
Send measurement
value cyclically
not active, 1 min
–
4 h
[20 min]
Setting whether and at what interval
the measured value is to be sent
cyclically.
Sensor
internal/external
▪
internal 100%
▪
external 10% / internal 90%
▪
external 20% / internal 80%
▪
…
▪
external 90% / internal 10%
▪
external 100%
Activation of an extension for
temperature measurement and
setting of the weighting between
internal and external sensor.
Calibration value for
internal sensor
-
50 … 50 x 0.1 K
[0]
Raise/lower the internal temperature
to correct the measured
temperature.
Temperature for upper
message value
not active
20 °C
–
45 °C
Activation of a message when a
certain temperature is exceeded.
Temperature for lower
message value
not active
3 °C
–
30 °C
Activation of a message when the
temperature falls below a certain
level.
Table 77: Settings
–
Temperature measurement