4.4.8 Mode selection
Single-Button function
Two-Button function
Important
: This function is only available for push-buttons with a temperature sensor.
The operating mode switchover function can be used to switch the HVAC mode in heating actuators
or temperature controllers.
The following picture shows the available settings (here for the two-button function):
Figure 33: Settings
–
Mode selection
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Toggle values
▪
Comfort / Standby
▪
Comfort / Night
▪
Comfort / Standby / Night
▪
Comfort / Standby / Night /
Frost protection
Setting between which operating
modes can be toggled.
Long keypress
▪
not active
▪
active
Activates an action for the long
keystroke
Action on left/right
button
▪
Comfort
▪
Standby
▪
Night
▪
Frost protection
Setting which operating mode is to
be called up with a long keystroke
of the left or right button.
Only with two-button function.
Action on long
keypress
▪
Comfort
▪
Standby
▪
Night
▪
Frost protection
Setting which operating mode is to
be called up with a long keystroke.
Only with single-button function.
Switching type
▪
limit stop (after the last
value, this is repeated)
▪
overrun (after the last value,
the first value is sent again)
Setting what should happen when
the last switching value is reached.
Only with two-button function.
Switchover considers
status object
▪
not active
▪
active
Setting whether the switchover is
to be carried out according to the
current status.