Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
51
51
4.4.5.4 Send value after state
Single-button function
The function "Send values - Send value after state" can send a fixed value according to the set
datapoint type and when the key is released a fixed value according to the set datapoint type.
The following figure shows the available settings:
Figure 33: Settings – Send values - Subfunction: Send value after state
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
2Bit DPT 2.001 Forcible control
1Byte DPT 5.001 Percent value
(0…100%)
1Byte DPT 5.005 Decimal factor
(0…255)
1Byte DPT 17.001 Scene number
2Byte DPT 7.600
Color temperature (Kelvin)
2Byte DPT 9.001 Temperature (°C)
2Byte DPT 9.004 Brightness (Lux)
3Byte DPT 232.600
RGB value 3x(0…255)
Sets the data point type to be
sent
Value for
pushed/released button
any value according to set data point
type
Setting the values to be sent
Table 38: Settings – Send values - Subfunction: Send value after state
The value to be sent can be set according to the set datapoint type for
pressing
and
releasing
the key.
The following table shows the available communication objects:
Number
Name
Length Usage
0
Push button 1 –
Forcible control, Percent value…
Sending the switching value.
DPT depending on the parameter setting
3
Push button 1 –
State for display
Receives the state.
DPT depending on the parameter setting.
Status for forcible control, scene number
and RGB value not available
Table 39: Communication objects – Send values - Subfunction: Send value after state