Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
69
69
Switchover considers
status object
Yes
No
Setting whether the changeover
should send the next switching
value according to the current
status
Status display
No status
HVAC-Mode
HVAC-Status
Sets how to output the status.
(
Parameters below the symbols,
see "Presentation" on the next
page
)
Table 62: Settings – Mode selection
Function principle:
The function "mode selection" can send up to 4 different operating modes by shortly pressing a
button. The operating modes are switched one after the other. Depending on the set parameters, for
example, at a keystroke the second operating mode is sent if the 1st operating mode has been sent
before or the third operating mode will be sent if the second operating mode has been sent before.
Parameter “Push button long”:
In addition to switchover by a short keystroke, a fixed operating mode can be sent at a long
keystroke.
Here one of the 4 operating modes can be sent. This means that a fixed operating mode
(independent of the last switching value) would always be sent with a long keystroke.
Parameter “Switching type”:
Limit stop:
With the switching type "Limit stop" the 4th operating mode is sent again after sending
the 4th operating mode.
Overrun:
In the switching type "Overrun", the 1st operating mode is sent again after the 4th
operating mode.
For the single-button function, this parameter is set permanently to "Overrun".
Switchover considers status object:
If the
status value is not taken into account
when switching over, the device remembers the last
value sent and sends the next or previous value the next time it is pressed, regardless of whether
another value has been sent to the object in the meantime.
If the
status value is taken into account
in the changeover, the device sends the next higher or next
lower changeover value - with reference to the last received status value - the next time it is pressed.
If, for example, the value "1K" was sent when the last key was pressed and then the value "2K" was
sent from another location, the value "2.5K" is sent the next time the "+" key is pressed.