Setpoint offset:
Because the Delta T- Control controls always with the current setpoint, the setpoint can be shifted or
set to a new value. Three methods to change the setpoint are available:
Setting a new absolute setpoint
By sending a temperature to the object 28, a complete new setpoint is set.
Shifting the current setpoint by sending a temperature difference
By sending a temperature difference to object 29, the setpoint is shifted in relation to the
current setpoint.
Shifting the setpoint in steps by using a 1 Bit command
B se di g a „ , the setpoi t is i reased the adjusted step ra ge a d se di g a „ ,
the setpoint is reduced by the adjusted step range.
The following table shows the communication objects for the automatic mode
–
Delta T:
Number
Name
Length
Usage
4
Control value failure
1 Bit
Showing a control value failure
5
Heating/Cooling
switchover
1 Bit
Switchover between heating/cooling; Showing
the current state
8
Manual setpoint offset
1 Bit
Shifts the setpoint by the adjusted step range
27
Temperature value
2 Byte
Receiving the current room temperature
28
Setpoint temperature
2 Byte
Sending a new absolute setpoint
29
Setpoint offset
2 Byte
Shifts the setpoint by a temperature difference
30
Current setpoint
temperature
2 Byte
State of the current setpoint
Table 53: Communication objects - Automatic mode Delta T