6.1.2 General FanCoil settings
The following figure shows the general settings:
Figure 38: General settings - FanCoil
The following settings are available:
ETS-text
Dynamic range
[default value]
comment
Send Heating/Cooling valve
cyclic
0-3600s
[0s]
Adjustment if the switching state of the
heating/cooling valve is sent cyclic
Changeover delay
50-5000ms
[200ms]
Setting for the delay between changing
the steps to avoid a simultaneously
control of 2 steps.
Have a look at the Datasheet of the
FanCoil!
Type of step switching
one after another
directly
Adjustment how the steps are
controlled:
one after another:
Level 0 is switched
on and is switched into Level3. Now the
Actuator switches into Level 3 in
compliance to the adjusted times as
follows: Level 1-> Level 2 -> Level 3
directly:
Level 0 is switched on and is
switched into Level3. Now the actuator
switches directly from level 0 to level 3.
Minimum holding time of each
step
0-1000s
[5s]
Defines how long one level is switched
on until the actuator changes into the
next level.