6.3.2 Automatic mode
–
Delta T
The following figure shows the available settings for the automatic mode via Delta T:
Figure 51: Automatic mode - Delta T
The following table shows the available settings:
ETS-text
Dynamic range
[default value]
comment
Release time to automatic
mode
0-1440
[0]
Defines the time which starts after
switching into the direct mode. When
this time is elapsed, the FanCoil
switches back into the automatic mode.
Monitoring time of control
value
0-360min
[0 min]
Defines the time periods in which the
actuator must receive a valid control
value. If no control value is received, a
control value failure is released and the
FanCoil switches into the step for a
FanCoil failure..