5.3.10 Manual switch off
The following illustration shows the setting options at the ETS-Software:
Figure 27: Manual switch off
By activation this function, you can switch the channel off before the staircase time runs out. For
s it hi g off the ha el, ou ha e to se d a logi al
to the o
u i atio o je t for s it hi g
the staircase function. When this function is not activated, the channel switches only off after the
staircase time runs out.
5.3.11 Extend time of staircase light
The following figure shows the available settings:
Figure 28: Extend time of staircase light
The following table shows the available settings:
ETS-text
Dynamic range
[default value]
comment
Extend time of staircase light
no extend time
restart time
add time
Setting if the staircase light can be
extended.
Table 37: Extend time of staircase light
The settings have the following functions:
No extend time
The staircase time cannot be extended. It is only possible to restart the staircase time after it
runs out.
Restart time
The stair ase ti e is restarted se di g a o
-
sig al to the o
u i atio o je t
stair ase light
.
Add time
The stair ase ti e is added to the re ai i g stair ase ti e he a e o
-
sig al is se t to
the o
u i atio o je t stair ase light .