5.3.10 Manual switch off 

 
The following illustration shows the setting options at the ETS-Software: 

 

Figure 27: Manual switch off 

By activation this function, you can switch the channel off before the staircase time runs out. For 

s it hi g off the  ha el,  ou ha e to se d a logi al 

 to the  o

u i atio  o je t for s it hi g 

the staircase function. When this function is not activated, the channel switches only off after the 
staircase time runs out. 
 

5.3.11 Extend time of staircase light 

 
The following figure shows the available settings: 

 

Figure 28: Extend time of staircase light 

 
The following table shows the available settings: 
ETS-text 

Dynamic range 

[default value] 

comment 

Extend time of staircase light 

 

no extend time 

 

restart time 

 

add time 

Setting if the staircase light can be 
extended. 

Table 37: Extend time of staircase light 

 
The settings have the following functions: 

 

No extend time 

The staircase time cannot be extended. It is only possible to restart the staircase time after it 
runs out. 

 

Restart time 

The stair ase ti e is restarted   se di g a   o

-

sig al  to the  o

u i atio  o je t 

stair ase light

 

Add time 

The stair ase ti e is added to the re ai i g stair ase ti e  he  a  e   o

-

sig al  is se t to 

the  o

u i atio  o je t  stair ase light .

 

 

 

Содержание AKK-03UP.02

Страница 1: ...logies GmbH Gesch ftsbereich Geb udeautomation Tel 49 2263 880 Fax 49 2263 4588 E Mail automation mdt de www mdtautomation de 1 Stand 03 2017 Technical Manual MDT Switch Actuator FanCoil AKK 03UP 02 A...

Страница 2: ...Usage 13 3 2 2 Default settings of the communication objects 18 4 Configuration of the operating mode 20 4 1 General Settings 20 5 Reference ETS Parameter Actuator 21 5 1 Channel selection 21 5 2 Swi...

Страница 3: ...1 2 General FanCoil settings 51 6 1 3 Blocking Functions 54 6 1 4 Activation of further submenus 55 6 2 Additional Ventilation 56 6 2 1 Automatic additional ventilation 56 6 2 2 Manual additional ven...

Страница 4: ...Technical Manual Switch Actuator FanCoil MDT technologies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 4 8 3 Assemblage 74 8 4 Datasheet 74...

Страница 5: ...e functions FanCoil Mode Controlling 3 three phase Fans 2 Blocking objects Additional ventilation Automatic mode via control value or Delta T available switching times individual adjustable AKK 04FC 0...

Страница 6: ......

Страница 7: ...63 880 Fax 49 2263 4588 knx mdt de www mdt de 7 2 4 Design Usage The AKK 03UP 01 is designed for flush mounting Contacting the loads can be done by using the connecting cables Furthermore the actuator...

Страница 8: ...P 01 2 6 Starting Up After wiring the allocation of the physical address and the parameterization of every channel follow 1 Connect the interface with the bus e g MDT USB interface 2 set bus power up...

Страница 9: ...atus DPT 1 011 send Actuator sends Operating Telgeram cyclic Diagnostic Object is shown when the cyclic Operating telegram is set to active Functions per channel 0 Channel A Switch on off DPT 1 001 re...

Страница 10: ...18 001 receive Actuator reacts to Incoming telegramm Push buttons Visu for manual control Communication onject appears only after activating scenes For calling of saved scenes which are saved in the...

Страница 11: ...ww mdt de 11 7 Channel A Logic 2 DPT 1 002 receive Actuator reacts to Incoming telegramm external switching state object of other devices Channel switches only On if the logic function of activated ob...

Страница 12: ...A Switch pulse 1 Bit Low X X 2 Channel A Block 1 Bit Low X X 4 Channel A Scene 1 Byte Low X X 5 Channel A Status 1 Bit Low X X X 6 Channel A Logic 1 1 Bit Low X X 7 Channel A Logic 2 1 Bit Low X X 11...

Страница 13: ...the maximum FanCoil Level at night General FanCoil objects 1 Switching Auto Manual 1 Automatic 0 Manual DPT 1 001 send receicve Actuator reacts to Incoming telegram and sends state at automatic switch...

Страница 14: ...Control value heating cooling DPT 5 001 receive Actuator reacts to incoming telegram Regulatio Communication object is shown at 2 Pipe systems and the automatic ode Co trol alue is a ti e Receiving t...

Страница 15: ...n unit Visu Push Butto Object can be activated at auto ati ode Delta T 27 Automatic mode Temperature value DPT 9 001 receive Actuator reacts to incoming telegram Temperature sensor Object is always sh...

Страница 16: ...ivated and switches the FanCoil one step down by recei i g a a d o e step up re ei i g a 10 Direct Mode Step 1 DPT 1 001 receive Actuator reacts to incoming telegram Central operation unit Visu Push B...

Страница 17: ...this state 18 Status Output Maximum control value for heating DPT 5 001 send Actuator sends state Visu Actuator Regulatio Object is shown when this state is active 19 Status Input Cascading Maximum c...

Страница 18: ...valve 1 Bit Low X X X 8 Automatic mode Manual setpoint offset 1 Bit Low X X 9 Direktbetrieb Step 0 1 Bit Low X X 9 Direktbetrieb Bit 0 1 Bit Low X X 9 Direktbetrieb Up Down 1 Bit Low X X 10 Direktbet...

Страница 19: ...9 Automatic mode Setpoint offset 2 Byte Low X X 30 Automatic mode Current setpoint temperature 2 Byte Low X X X 46 Operating Send Status 1 Bit Low X X 47 Day Night Switching 1 Bit Low X X Table 4 Comm...

Страница 20: ...1 General Settings The following table shows the general settings for the AKK 03UP 01 ETS text Dynamic range default value comment Startup timeout 0 120s 5s Time between a reset and the functional sta...

Страница 21: ...le 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 21 5 Reference ETS Parameter Actuator 5 1 Channel selection Every channel can be selected as Switch or as Staircase function at the sub menu...

Страница 22: ...ting options for this parameter Figure 6 Operating mode The following chart shows the dynamic range for this parameter ETS text Dynamic range default value comment Mode normally opened normally closed...

Страница 23: ...unction can be switched on off for every channel For switching on this function you ha e to hoose the optio a ti e B alli g the e tral o u i atio o je t all ha els ith a activated central function are...

Страница 24: ...as the channel is locked By sending a logical 0 the channel can be unlocked again The following actions can be performed at locking unlocking no change The channel stays in the current state On The ch...

Страница 25: ...2 Behavior at bus power down up 5 2 5 On Off delay The following illustration shows the setting options at the ETS Software Figure 10 On Off delay The on delay causes a delayed switch of the channel A...

Страница 26: ...state is available no send passive state object The state object does not send its current state and can only be requested at change The state object sends its current state at every change of the out...

Страница 27: ...us state Setting of the behavior after deactivating priority forced control Table 15 Priority Forced control The priority forced operation cause the priority switching of output By using the release t...

Страница 28: ...ditional logic objects The logical function AND OR XOR and Gate functions are available Figure 14 Logic function schematic diagram The logical functions switch the output if the followings conditions...

Страница 29: ...ut output can be inverted The para eter et o je t alue after us po er up defi es if the logi is set to a fi ed alue after a bus power return The following table shows the available communication objec...

Страница 30: ...ub menu for the scenes appears at the left drop down menu There are settings to activate single scenes set values and scene numbers and switch the memory function on off at this sub menu Scenes are ac...

Страница 31: ...ies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 31 There are up to 8 storage options for scenes at every channel These 8 storage options can get any o...

Страница 32: ...or saving a new value for the scene you have to send the accordingly code to the relevant communication object for the scene Scene Retrieve Save Hex Dez Hex Dez 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0...

Страница 33: ...mode The following illustration shows the setting options for this parameter Figure 17 Operating mode The following chart shows the dynamic range for this parameter ETS text Dynamic range default val...

Страница 34: ...tral function can be switched on off for every channel For switching on this function you ha e to hoose the optio a ti e B alli g the e tral o u i atio o je t all ha els ith a activated central functi...

Страница 35: ...e locking object and further control is no longer available as long as the channel is locked By sending a logical 0 the channel can be unlocked again The following actions can be performed at locking...

Страница 36: ...turns Behavior at bus power down Off On no change Defines the behavior when bus power is dwon Table 26 Behavior at bus power down up The following actions can be performed at locking unlocking no chan...

Страница 37: ...state object does not send its current state and can only be requested at change The state object sends its current state at every change of the output at change and lock The state object sends its cu...

Страница 38: ...l into the normal state Behavior after forced control priority Off no change start time of staircase light Setting of the behavior after deactivating priority forced control Table 29 Priority Forced c...

Страница 39: ...ew sub menu for the scenes appears at the left drop down menu There are settings to activate single scenes set values and scene numbers and switch the memory function on off at this sub menu Scenes ar...

Страница 40: ...ies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 40 There are up to 8 storage options for scenes at every channel These 8 storage options can get any o...

Страница 41: ...or saving a new value for the scene you have to send the accordingly code to the relevant communication object for the scene Scene Retrieve Save Hex Dez Hex Dez 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0...

Страница 42: ...actor staircase time If a value of 10s is set and the value 55 is sent the staircase light is started with a time of 550seconds The variable staircase time can be used for starting the staircase time...

Страница 43: ...ed o agai Table 35 Prewarning function The settings for the warning have the following behavior Light On Off The light is switched off for the adjusted prewarning duration after the staircase time run...

Страница 44: ...runs out 5 3 11 Extend time of staircase light The following figure shows the available settings Figure 28 Extend time of staircase light The following table shows the available settings ETS text Dyna...

Страница 45: ...figure shows the available settings Figure 29 Additional switching object By activating the switch object an additional switching object is shown which works independently from the staircase light Th...

Страница 46: ...ing illustration shows the setting options for this parameter Figure 30 Operating mode The following chart shows the dynamic range for this parameter ETS text Dynamic range default value comment Mode...

Страница 47: ...ETS text Dynamic range default value comment Pulse time 300ms 30s 500ms Setting of the duration of the pulse Repeat pulse signal once not active active Setting if the pulse is repeated once Time to n...

Страница 48: ...pulse Behavior at deactivating the locking function Table 42 Locking function A Channel is locked by sending a logical 1 to the locking object and further control is no longer available as long as the...

Страница 49: ...pe only heating The following image shows a 2 Pipe system for a heating mode The FanCoil is controlled directly from the FanCoil Actuator AKK 03UP 01 The heating valve is switched by a separate actuat...

Страница 50: ...is switched by a separate actuator which is controlled by object 6 According to the mode heating or cooling the heating or cooling supply is switched on Figure 36 2 Pipe System Heating and Cooling 4...

Страница 51: ...over delay 50 5000ms 200ms Setting for the delay between changing the steps to avoid a simultaneously control of 2 steps Have a look at the Datasheet of the FanCoil Type of step switching one after an...

Страница 52: ...the minimum time in the starting step if the switch on behavior is not set to direct start Off Delay of the fan 0 1000s 0s Defines the off delay of the Fan when it was switched off for using the resid...

Страница 53: ...tches into the next level In this example step 3 is switched on and step 0 is active The steps are driven in succession Figure 40 Minimum holding time of each step Switch On behavior If the FanCoil mu...

Страница 54: ...ng but the FanCoil is switched after the Off Delay is elapsed Figure 42 Off Delay The following table shows the available communication objects for these parameters Number Name Length Usage 6 Switch h...

Страница 55: ...no reaction switch to step 1 switch to step 2 switch to step 3 restore previous step Memory function no reaction The FanCoil is blocked for further control and stays in the current step Switch to step...

Страница 56: ...justed cycle time 6 2 2 Manual additional ventilation The following figure shows the available settings for the manual additional ventilation Figure 46 Manual additional ventilation The manual additio...

Страница 57: ...1 Bit Switchover between automatic and manual mode Table 49 Communication object Switchover Auto Manual The FanCoil actuator reacts only to control values or temperature values if the automatic mode i...

Страница 58: ...alue the FanCoil switches into step 1 Threshold for fan step 2 0 100 50 Defines from which value the FanCoil switches into step 2 Threshold for fan step 3 0 100 80 Defines from which value the FanCoil...

Страница 59: ...t Mode The FanCoil actuator switches because of the manual switching command into the manual mode Now the release time switches the FanCoil actuator back into the automatic mode after the adjusted tim...

Страница 60: ...Technical Manual Switch Actuator 3 fold FanCoil MDT technologies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 60 Figure 49 Thresholds Control value...

Страница 61: ...ching from heating into cooling Figure 50 Dead time at heating cooling switchover The following table shows the communication objects for the automatic mode control value Number Name Length Usage 2 Co...

Страница 62: ...table shows the available settings ETS text Dynamic range default value comment Release time to automatic mode 0 1440 0 Defines the time which starts after switching into the direct mode When this ti...

Страница 63: ...um setpoint offset Setpoint offset by 1 Bit object not active active The setpoint offset via 1 Bit object i reases the setpoi t at re ei i g a by the adjusted step range and reduces the setpoi t at re...

Страница 64: ...ftware At Figure 52 Thresholds Delta T the thresholds are set to 1K 2K and 3 5K The threshold for switching into the next lower step are calculated via threshold hysteresis Here the hysteresis is set...

Страница 65: ...setpoint in steps by using a 1 Bit command B se di g a the setpoi t is i reased the adjusted step ra ge a d se di g a the setpoint is reduced by the adjusted step range The following table shows the...

Страница 66: ...nication objects Direct mode binary coded 6 4 2 Step switch At the step switch every step is controlled by a separate communication object If a communication object receives a logical 1 at one communi...

Страница 67: ...n be used If the current step is selected the state shows always the actual step Because of the times for changeover delay minimum time of each time etc a delay between feedback and state function can...

Страница 68: ...3 External heating request Input 1 Bit Input for cascading the heating request 14 External heating request Output 1 Bit Output of the heating request 15 External cooling request Input 1 Bit Input for...

Страница 69: ...fan level cooling Input 1 Bit Input for cascading the maximum Fan Level in cooling mode 24 Maximum fan level cooling Output 1 Bit Output of the maximum Fan Level in cooling mode Table 62 Communication...

Страница 70: ...de 33 Figure 18 Central function 34 Figure 19 Locking function 34 Figure 20 Behavior at bus power down bus power up 35 Figure 21 State functions 36 Figure 22 Priority Forced control 38 Figure 23 Scene...

Страница 71: ...6 Figure 46 Manual additional ventilation 56 Figure 47 Automatic Mode Control value 57 Figure 48 Release time to automatic mode 59 Figure 49 Thresholds Control value 60 Figure 50 Dead time at heating...

Страница 72: ...ble 20 Calling and saving scenes 32 Table 21 Operating mode 33 Table 22 Central function 34 Table 23 Communication object central function 34 Table 24 Behavior at locking unlocking 35 Table 25 Communi...

Страница 73: ...mode Delta T 65 Table 54 Direct Mode binary coded 66 Table 55 Communication objects Direct mode binary coded 66 Table 56 Communication object Direct mode step switch 66 Table 57 Communication objects...

Страница 74: ...occur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 8 2 Routine disposal Do not throw the waste equ...

Страница 75: ...of bus voltage failure or return The MDT Switch Actuator AKK Fancoil is a modular installation device for ixed installations in dry rooms It its on DIN 35mm rails in power distribution boards or clos...

Страница 76: ...transformers 10 Output life expectancy mechanical 1 000 000 Max total current of the actuator 16A Speciication KNX interface TP 256 with long frame support for ETS5 Available application software ETS...

Страница 77: ...uses a bistable relay and is individually agjustable via ETS In aoperation mode as fan coil actuator a 3 step ventilators is controlled Fan coil mode Control of 3 speed fans ventilator convectors Outp...

Страница 78: ...transformers 2 Output life expectancy mechanical 1 000 000 Max total current of the actuator 16A Fuse protection 10A Speciication KNX interface TP 256 with long frame support for ETS5 Available applic...

Отзывы: