70
MDS NETio Installation & Operation Guide
MDS 05-4457A01, Rev. A
For wiring information on Type 7 Modules, refer to
Table 4-8
below,
and the following sections in this manual:
•
Section 4.2.1,
Analog Input Wiring
for connecting analog
inputs.
•
Section 4.2.2,
Discrete Points Wiring
for connecting discrete
input or output points
Table 4-8. NETio-XM-7 Expansion Module I/O Terminations
Functions: 1DI, 3DO, 2AI (I)
TERM
FUNCTION
TERM
FUNCTION
TERM
FUNCTION
TERM
FUNCTION
01
POWER +
05
Ain 1 +
09
Dout 1 +
13
Din 1 +
02
POWER –
06
Ain 1 –
10
Dout 1 –
14
Din 1 –
03
GROUND
07
Ain 2 +
11
Dout 2 +
15
Dout 3 +
04
GROUND
08
Ain 2 –
12
Dout 2 –
16
Dout 3 –