background image

Page 32 / IM 178

Sequences of Operation

The following sequences of operation are for a typical “C”
vintage applied rooftop unit that is equipped with an econo-
mizer, a return air fan, a MicroTech controller, an external
time clock, and a Remote Monitor Panel. These sequences
describe the ladder wiring diagram logic in detail; refer to the
schematics in the “Wiring Diagrams” section as you read
them. Note that your unit’s sequences of operation may vary

from those described here. Refer to the wiring diagrams
supplied with the unit for exact information.

For a detailed description of operation information relat-

ing to the MicroTech controller’s software, refer to the
appropriate operation manual (see Table 1). These manuals
describe the various set points, parameters, operating states,
and control algorithms that affect rooftop unit operation.

Power-up

When the outdoor air is suitable for free cooling, the switch
in enthalpy sensor OAE is in position “3” (line 254), and thus
digital input D0 (terminal DH1-0) on the ADI board is ener-
gized. When DH-1 is energized, the economizer is enabled.
If cooling is required, the economizer dampers (ACT3) are
modulated to maintain the discharge air temperature set
point. When energized, output relay OBA8 opens the out-
door air dampers, and OBA7 closes them (line 338). If the
outdoor air dampers are wide open and more cooling is

required, the dampers will hold their positions and mechani-
cal cooling will be activated (see below).

When the outdoor air is not suitable for free cooling, the

switch in enthalpy sensor OAE is in position “1”, and thus
digital input D0 (terminal DH1-0) on the ADI board is de-
energized. When DH1-0 is de-energized, the economizer is
disabled and the dampers are then held at their minimum
position.

Economizer Operation

Fan Operation

When the supply and return fans are commanded to start by
the microprocessor control board MCB1, the unit enters the
Start-up Initial operating state. As a result, a 3-minute timer
is set, solid-state output relay OBA15 energizes, relay R26
energizes (line 328), and the occupied output contacts close
(line 395). On VAV units, output relays OBA10 and OBA12
energize (line 343), causing the supply and return fan inlet
vanes to open. When the vanes open to their minimum
positions, OBA10 and OBA12 are de-energized, causing the
inlet vanes to hold.

After the 3-minute timer expires, the unit enters the

Recirculate operating state. As a result, output relay OBA13
energizes (line 301), causing supply fan contactors M9 and
M10 to energize. Four seconds after OBA13 is energized,
output relay OBA14 energizes (line 303), causing return fan
contactors M19 and M20 to energize. Overload relays OL9,
OL10, OL19, and OL20 (line 301) protect the fans from
excessive current draw. If either the supply or return fan is
drawing excessive current, one of the relays will open its
contacts and cause both fans to stop.

Within 30 seconds after the fans start, the controller

expects airflow switch PC7 (line 263) to close and thus

energize digital input D8 (terminal DH1-8) on the ADI board.
(If DH2-8 does not energize, the controller will assume the
fans did not start. It will then shut down the unit and generate
an alarm.)

During the Recirculate operating state, the outside air

damper is held closed. The controller does this by energizing
output relay OBA7 (line 338). On VAV units, output relay
OBA6, the VAV box output, is also energized (line 395) during
the Recirculate state.

On VAV units, the supply fan vanes (ACT1) are modulated

to maintain the duct static pressure set point. When ener-
gized, output relay OBA10 opens them, and OBA9 closes
them (line 343). On VAV units or CAV units equipped with
return fan inlet vanes, the return fan vanes (ACT2) are
modulated to maintain an acceptable building static pres-
sure. When energized, output relay OBA12 opens them, and
OBA11 closes them (line 343). (Switch S6 on line 342 is
provided for supply/return fan airflow balancing which is part
of the unit check, test, and start  procedure.)

Note: The “Typical Actuator Control Circuit” schematic

shows the modulating hot water or steam heat (VM1) option
that is not discussed here.

• external exhaust fan status contacts (line 257)
• Remote Monitor Panel on-off switch (line 259)
• Remote Monitor Panel heat-auto-cool switch (lines 259

and 262)

• airflow interlock switch PC7 (line 263)
• dirty filter switches PC5 and PC6 (lines 264 and 265)
• compressor safety relays R5 and R6 (lines 266-270)
• duct high limit switch DHL (line 272, VAV and CAV-DTC

only)

• gas furnace alarm relay R24 (line 275)
• freezestat switch FS1 (line 278)
• smoke detectors SD1 and SD2 (line 281)

When the fan switch on the Remote Monitor Panel is in the

“off” position, field wiring terminals 105 and 106 (lines 259
and 262) are de-energized. These respective terminals are
connected to the cool enable digital input D3 (terminal DH1-
3) and the heat enable digital input D4 (terminal DH1-4) on the
ADI board. If terminals DH1-3 and DH1-4 are both de-
energized, the MicroTech controller disables fan operation
because it assumes the fan switch is off. If either terminal
DH1-3 or DH1-4 is energized, the MicroTech controller enables
fan operation because it assumes the fan switch is on.

When primary power is connected to the unit, 115 VAC power
is fed through contact circuit transformer T1 and control
circuit fuse F1 (line 200) to compressor crankcase heaters
HTR-1 and HTR-2 (lines 805 and 855).

When system switch S1 (line 205) is closed, low voltage

transformers T2 (line 203) and T3 (line 208) are energized,
and 115 VAC power is supplied to the following:
• economizer actuator ACT3 (line 336)
• supply fan vane actuator ACT1 (line 340, VAV only)
• return fan vane actuator ACT2 (line 346, VAV only)
• compressor circuit switches CS1 and CS2 (lines 807 and

857)

• unit manual pumpdown switch PS3 (line 328)

Transformer T3 supplies 18 VAC center-tapped power to

the power in terminals 1, 2 and 3 on the microprocessor
control board MCB1 (line 210). By way of terminal TB6-47
(lines 207 and 251), transformer T2 supplies 24 VAC power
to the following:
• static pressure sensor SPS1 (line 230, VAV only)
• static pressure sensors SPS2, SPS5, SPS6 (lines 232-236)
• enthalpy sensor OAE (line 254)
• external time clock contacts (line 256)

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание RoofPak RDS 802C

Страница 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Страница 2: ...1 Date January 1997 Installation Maintenance Data RoofPak Applied Rooftop Systems Air Handler RDS 800C 802C 1997 McQuay International L I S T E D L I S T E D C Artisan Technology Group Quality Instrum...

Страница 3: ...ntrol Circuit CAV ZTC Units 37 Typical Main Control Circuit CAV DTC Units 38 Typical Actuator Control Circuit 39 Typical Supply Return Fan Control Circuit 39 Typical Gas Furnace Control Circuit 40 Mod...

Страница 4: ...AV OM 108 Constant Air Volume Zone Temperature Control CAV ZTC OM 109 Constant Air Volume Discharge Temperature Control CAV DTC OM 110 When the equipment is received all items should be carefully chec...

Страница 5: ...ol Entrances Outside Return Air Dampers Exhaust Hood Main Control Panel Discharge Plenum Cooling Coil Outside Air Louvers Return Air Fan Supply Air Fan Filter Section Heat Section Natural Gas Oil Stea...

Страница 6: ...luded in the Wiring Diagrams section of this manual Figure 2 Control locations Return Air Economizer Filter Section Supply Fan Section Blow through Heat Section Blow through Coil Section Discharge Ple...

Страница 7: ...6 SPS1 SPS2 NB1 DHL ADI SB1 OBB OBA T1 FB10 FB20 M20 M10 OL20 OL10 FB8 TB8 TB7 DSI or PB1 TB10 TB5 NB2 TB1 TB2 TB2 MCB1 T2 Main control panel Supply Fan Section Main Control Panel Electric Heat Contro...

Страница 8: ...age 7 Electric heat control panel TB12 M43 M42 M41 FB43 FB42 FB41 M33 M32 M31 FB33 FB32 FB31 HL4 HL14 T5 SR1 SR2 SR3 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artis...

Страница 9: ...B or C 16 position 665422B 02 8 position 665422B 03 4 position PC5 6 Filter switch Turns on clogged filter light on status panel Auto Filter sections As required 05 5 w c 05 w c 654938B 01 12 5 1245...

Страница 10: ...allow flow of gas to pilot burner Normally Gas heating section N A N A N A 344884B 00 closed GV2 3 Main gas valves Open to allow flow of gas to main burner Normally Gas heating section N A N A N A See...

Страница 11: ...shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes Sharpedge...

Страница 12: ...box b Overhead obstructions shall be no less than 2 51 mm above the top of the unit c There shall be no overhead obstructions in the areas above the outside air and exhaust dampers that are farther t...

Страница 13: ...arts E and F are not required on units with no return shaft within the curb perimeter 9 Parts G and H are not required on units with no supply shaft within the curb perimeter 38 8 984 7 5 191 2 51 X I...

Страница 14: ...distance A Lift Only As Indicated Maximum recommended width for structural member is 5 127 mm to allow for adequate space for duct connections and electrical entry Rigging and Handling Lifting bracket...

Страница 15: ...ension Z i e A Z X Y Where Z Total unit length in inches refer to certified drawings for this dimension X Outdoor return air section length refer to Table 3 for this dimension If A 288 7315 mm 4 point...

Страница 16: ...e Unit Descrip tion section of this manual The duct static pressure sensing tap must be carefully located and installed Improper location or installation of the sensing tap will cause unsatisfactory o...

Страница 17: ...ence pressure LO tap on the roof Keep it away from the condenser fans walls or anything else that may cause turbulence Mount it high enough above the roof so that it is not affected by snow If the ref...

Страница 18: ...nimize This Dimension Note Drain line must not be run higher than this level A 8 203 mm Min or 2 x P Copper Tube one each end of coil See View A View A Drain Pan Static Pressure P in w c RDS units tha...

Страница 19: ...and there are no refrigerant leaks the system should be evacuated The use of a vacuum pump with a pumping capacity of approxi mately 3 cu ft min and the ability to reduce the vacuum in the unit to at...

Страница 20: ...each circuit Note The total operating charge per circuit should not exceed the pumpdown capacity per circuit specified by the condensing unit manufacturer Table 6 Approximate refrigerant charge per c...

Страница 21: ...a fin height of 39 991 mm A factory installed three way valve piping and motor actuator is available for hot water coils in a heating only section see Figure 13 When no factory piping or valve is incl...

Страница 22: ...erally the vacuum breaker is to be connected between the coil inlet and the return main However if the system has a flooded return main the vacuum breaker should be open to the atmosphere and the trap...

Страница 23: ...unit and vestibule with silicone sealant along top and sides as shown Note Any holes cut in the floor of the unit must be sealed to prevent water leakage Figure 16d Step 3 1 Assemble side panels A an...

Страница 24: ...s through a 90 degree angle to bring the economizer dampers from full open to full close Mechanical stops have been placed in the crankarm mounting bracket Do not remove stops If the crankarm is drive...

Страница 25: ...tact the adjoining blade The blades will lock up if they are closed so far the seal goes over center 75 Figure 19 Intake hood damper 0 to 30 outside air These dampers are intended to remain at a fixed...

Страница 26: ...atherproof opera tion After the unit has been set in place all door gaskets should be inspected for shipping damage and replaced if necessary It is recommended the unit be protected from overhead runo...

Страница 27: ...uits can penetrate the cabinet bottom base frame or through the hinge and latch cap without interfering with the access panels Note All holes cut into the unit must be sealed to prevent water leakage...

Страница 28: ...on the unit If side entrance is the only option a drilling location is provided The drilling dimen sions must be followed exactly to prevent damage to the control panel The dimensions provided are the...

Страница 29: ...r death Connect only low voltage NEC Class II circuits to termi nal blocks TB2 and TB7 Reinstall and secure all protective deadfront panels when the wiring installation is complete Most field control...

Страница 30: ...sure plug in the louvered fresh air intake area Replace the closure plug after removing lock down bolt All four bolts on each fan assembly must be removed Adjustment of spring mounts Each spring mount...

Страница 31: ...After the spring mounts have been adjusted for level opera tion the thrust restraints should be checked With the fan off the adjustment nuts should be set so the spring is slightly compressed against...

Страница 32: ...located next to each spring isolator These snubbers will allow free movement of the fan assem blies during normal operation because normal operation will not cause fan movements that exceed 25 6 mm H...

Страница 33: ...n the ADI board If DH2 8 does not energize the controller will assume the fans did not start It will then shut down the unit and generate an alarm During the Recirculate operating state the outside ai...

Страница 34: ...energizing relay R20 and opening its contacts in line 610 As a result the flame safeguard control is de energized all gas valves close the combustion air blower motor stops and gas valve actuator VM1...

Страница 35: ...ensor Discharge Bulkhead OBA Output Board A Standard Main Control Box OBB Output Board B Cooling Main Control Box OBC Output Board C Heating Main Control Box OL9 10 Overload Relays Supply Fan Main Con...

Страница 36: ...IM 178 Page 35 Typical Power Circuit Typical Compressor Staging Outputs Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 37: ...Page 36 IM 178 Typical Main Control Circuit VAV Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 38: ...IM 178 Page 37 Typical Main Control Circuit CAV ZTC Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 39: ...Page 38 IM 178 Typical Main Control Circuit CAV DTC Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 40: ...IM 178 Page 39 Typical Actuator Control Circuit Typical Supply Return Fan Control Circuit Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 41: ...o indicate operation Low fire start is provided by relay R23 The relay drives the gas valve actuator VM1 to the minimum firing rate position whenever the flame is not on and holds it there until the f...

Страница 42: ...IM 178 Page 41 Typical Electric Heat Control Circuit Multistage Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 43: ...t is on when all phase voltages are within specified limits The phase voltage monitor is located on the load side of the power block with a set of contacts wired to the 115 volt control circuit to shu...

Страница 44: ...eating valve will close If the freezestat closes again the heating valve will open and the 10 minute timer will reset The unit will remain shut down until the Freeze Stat Fail alarm is manually cleare...

Страница 45: ...ontrols on both the supply and return fan it is important that both actuators have exactly 180 degree rotation to assure proper tracking of the two actuators NOTICE Inlet vanes must not be adjusted to...

Страница 46: ...To Open 20 Closed Open 2 78 View 1 30 Wheel 800C 802C View 2 40 Wheel 802C Closed Open 60 A B X 3 00 20 Wheel 800C 2 80 24 Wheel 802C 180 CW To Open X 24 Closed Open Adjustable 11 8 28 mm slot Figure...

Страница 47: ...el 7 If unit is curb mounted verify that the curb is properly flashed to prevent water leakage 8 Before attempting to operate the unit review the control layout description to become familiar with the...

Страница 48: ...ing system switch S1 Economizer Start up Improper adjustment may damage the dampers Assure proper damper adjustment When an economizer is ordered without an actuator the linkage requires a 3 14 linear...

Страница 49: ...re than five full turns for A belts or six full turns for B belts Adjust both halves of two groove sheaves by the same number of turns from closed to ensure that both grooves have the same pitch diame...

Страница 50: ...isfac tory locking of the sheave If locking screws A are removed by accident and the gap is lost screw the outer locking ring down until it touches the inner locking ring Then back off the outer ring...

Страница 51: ...e operating schedule as required keypad menus 25 and 26 15 Place the unit into the Calibrate mode by selecting it from keypad menu 11 Control Mode Calibrate will automatically zero all pressure sensor...

Страница 52: ..._______ 14 Htg Control VAV CAV DTC Set Point ____ F ___________ Max OAT ____ F ___________ Programs ART1 ART2 ART3 Min Spt ____ F ___________ ART4 ART6 and ART8 Max Spt ____ F ___________ Reset No Res...

Страница 53: ...ime ____ Sec ___________ and ART6 Mod Lim ____ WC ___________ Wait Time ____ Sec ___________ Max Step ____ Sec ___________ 20 Fan Balance VAV with fan Balance Off ___________ tracking control On Set M...

Страница 54: ..._______ Sun hr mn hr mn ___________ Mon hr mn hr mn ___________ Tue hr mn hr mn ___________ Wed hr mn hr mn ___________ Thu hr mn hr mn ___________ Fri hr mn hr mn ___________ Sat hr mn hr mn ________...

Страница 55: ...n ___________ 28 Service Mode Normal ___________ Shutdown Timers Normal ___________ Fast Space Sensor No ___________ Yes OAT Local ___________ Remote Duct Sensor 2 No ___________ Yes Alarm Out Blink _...

Страница 56: ...and control voltages 8 Check the running amperage of all motors 9 Check all operating temperatures and pressures 10 Check and adjust all temperature and pressure controls as needed 11 Check and adjus...

Страница 57: ...o assure that they have not loos ened If this is not done severe equipment damage could occur Using Table 16 check the tightness of all setscrews with a torque wrench Note that if the return fan beari...

Страница 58: ...5 25 Funnel Wheel 18 9 31 9 31 Wheel Funnel C L Fan Winterizing Water Coils Coil freeze up can be caused by such things as air stratifica tion and failure of outdoor dampers and or preheat coils Routi...

Страница 59: ...your nearest McQuay representa tive The order should include the component s part number and description and the model and serial numbers of the unit involved If it is determined that the failure of...

Страница 60: ...f all other warranties There is no implied warranty of merchantability or fitness for a particular purpose In no event and under no circumstances shall the Company be liable for incidental or conseque...

Страница 61: ...ard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330 Printed on recycled paper containing at least 10 post consumer recycled material Artisan Technology Group Quality Instrumentation Guaranteed 888...

Страница 62: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Отзывы: