background image

Page 34 / IM 178

Wiring Diagrams

Wiring Diagrams

Legend

Designation

Description

Std. Location

ACT1 .................. Actuator Motor, Supply Fan Vanes ............................ Supply Air Sect.
ACT2 .................. Actuator Motor, Return Fan Vanes ............................ Return Air Sect.
ACT3, 4 .............. Actuator Motors, Economizer Dampers .................... Economizer Sect.
ACT5 .................. Actuator Motor, Discharge Isolation Damper ........... Discharge Sect.
ACT6 .................. Actuator Motor, Return Air Isolation Damper ........... Return Air Sect.
ACT7, 8 .............. Actuator Motors, Face & Bypass Dampers .............. Coil Sect.
ACT 10, 11 ........ Actuator Motors, Exhaust Dampers .......................... Return Air Sect.
ADI ..................... ADI Board ................................................................... Main Control Box
AFD10 ................ Adj. Freq. Drive, SupplyFan ....................................... AFD Access Sect.
AFD20 ................ Adj. Freq. Drive, Return Fan ...................................... AFD Access Sect.
AS ...................... Blower Air Switch ....................................................... Furnace Sect.
BM ..................... Burner Blower Motor ................................................. Furnace Sect.
C9, 10 ................ Power Factor Capacitors, Supply Fan ...................... Supply Air Sect.
C19, 20 .............. Power Factor Capacitors, Return Fan ...................... Return Air Fan
DHL .................... Duct High Limit .......................................................... Main Control Box
DS1 .................... Disconnect, Total Unit or Heat .................................. Main Control Box
DS2 .................... Disconnect, SAF/RAF/Controls ................................. Main Control Box
DS3 .................... Disconnect, Electric Heat .......................................... Electric Heat Sect.
F1 ....................... Fuse, Control Circuit .................................................. Main Control Box
F3 ....................... Fuse, Burner Motor .................................................... Main Control Box
FB8 .................... Fuseblock, Main Transformer .................................... Main Control Box
FB9, 10 .............. Fuseblocks, Supply Fan ............................................ Main Control Box
FB19, 20 ............ Fuseblocks, Return Fan ............................................. Main Control Box
FB31-40 ............. Fuseblocks, Electric Heat (Top Bank) ....................... Electric Heat Sect.
FB41-50 ............. Fuseblocks, Electric Heat (Bottom Bank) ................. Electric Heat Sect.
FD ...................... Flame Detector ........................................................... Furnace Sect.
FLC .................... Fan Limit Control ........................................................ Furnace Sect.
FS1 .................... Freezestat Control ...................................................... Heat Sect.
FSG .................... Flame Safeguard ........................................................ Furnace Sect.
GFS1/GFR1 ....... Ground Fault Sensor/Relay, RPS Unit ...................... Main Control Box
GRD ................... Ground ........................................................................ All Control Boxes
GV1 .................... Gas Valve, Pilot .......................................................... Furnace Sect.
GV2, 3 ................ Gas Valves, Main ........................................................ Furnace Sect.
HL1-10 ............... High Limits, Elec. Heaters, Power (Top Bank) .......... Electric Heat Sect.
HL11-20 ............. High Limits, Elec. Heaters, Power (Bottom Bank) .... Electric Heat Sect.
HL22 .................. High Limit, Gas Heat (Prefilters) ................................ Supply Air Sect.
HL23 .................. High Limit, Gas Heat (Final Filter) .............................. Final Filter Sect.
HL31-40 ............. High Limits, Elec. Heaters, Control (Top Bank) ........ Electric Heat Sect.
HL41-50 ............. High Limits, Elec. Heaters, Control (Bottom Bank) .. Electric Heat Sect.
HP5 .................... High Pressure Control, Gas ....................................... Furnace Sect.
HS1 .................... Heat Switch, Electric, Shutdown ............................... Main Control Box
IT ........................ Ignition Transformer ................................................... Furnace Sect.
LP5 .................... Low Pressure Control, Gas ........................................ Furnace Sect.
LT2 ..................... Light, Furnace On ...................................................... Furnace Sect.
LT3 ..................... Light, Pilot Gas Valve On ........................................... Furnace Sect.
LT4 ..................... Light, Main Gas Valve On .......................................... Furnace Sect.
LT10 ................... Light, Supply Fan ....................................................... Supply Air Sect.
LT11 ................... Light, Return Fan ....................................................... Return Air Sect.
LT12 ................... Light, Heat Section .................................................... Heat Sect.
LT13 ................... Light, Filter Section .................................................... Filter Sect.
LT14 ................... Light, Final Filter Section ........................................... Final Filter Sect.
LT15 ................... Light, Discharge Section ............................................ Discharge Sect.
LT16 ................... Light, Blow-through Coil Section .............................. Blow-thru Coil Sect.
LT17 ................... Light, Evaporator Coil Section .................................. Evaporator Coil Sect.
LT18 ................... Light, Preheat Section ............................................... Preheat Sect.
LT19 ................... Light, Blank Section ................................................... Blank Sect.
LT20 ................... Light, Blank Compartment ......................................... Blank Compartment
LT21 ................... Light, Draw-through Coil Section .............................. Draw-thru Coil Sect.
M9, 10 ................ Contactors, Supply Fan ............................................. Main Control Box
M19, 20 ............. Contactors, Return Fan ............................................. Main Control Box
M29 .................... Contactor, Burner Motor ............................................ Furnace Sect.
M30 .................... Contactor, Supply AFD Bypass ................................. AFD Access Sect.
M31-39 .............. Contactors, Elec. Heaters (Top Bank) ....................... Electric Heat Sect.
M40 .................... Contactor, Return AFD Bypass ................................. AFD Access Sect.
M41-50 .............. Contactors, Elec. Heaters (Bottom Bank) ................. Electric Heat Sect.
MAT .................... Mixed Air Temperature Sensor .................................. Supply Air Sect.
MCB1 ................. Microprocessor Control Board #1 ............................. Main Control Box
MJ ...................... Mechanical Jumpers .................................................. Terminal Blocks
NB1, 2 ................ Neutral Blocks ............................................................ Main Control Box

Designation

Description

Std. Location

OAE .................... Outside Air Enthalpy Control ..................................... Economizer Sect.
OAT .................... Outside Air Temperature Sensor ............................... Discharge Bulkhead
OBA ................... Output Board A, Standard ......................................... Main Control Box
OBB ................... Output Board B, Cooling ........................................... Main Control Box
OBC ................... Output Board C, Heating ........................................... Main Control Box
OL9, 10 .............. Overload Relays, Supply Fan .................................... Main Control Box
OL19, 20 ............ Overload Relays, Return Fan ..................................... Main Control Box
PB1 .................... Powerblock, Total Unit or Heat .................................. Main Control Box
PB2 .................... Powerblock, SAF/RAF/Controls ................................ Main Control Box
PB3 .................... Powerblock, Electric Heat ......................................... Electric Heat Sect.
PB9, 10 .............. Powerblocks, Supply Fan .......................................... Unit Split Jct. Box
PB19, 20 ............ Powerblocks, Return Fan .......................................... Unit Split Jct. Box
PC5 .................... Pressure Control, Clogged Filter ............................... Filter Sect.
PC6 .................... Pressure Control, Clogged Final Filter ...................... Final Filter Sect.
PC7 .................... Pressure Control, Proof of Airflow ............................. Supply Air Filter
PC8 .................... Pressure Control, Minimum Airflow ........................... Evaporator Coil Sect.
PM1 ................... Phone Modem ............................................................ Main Control Box
PVM1 ................. Phase Voltage Monitor, RPS Unit .............................. Main Control Box
R20 .................... Relay, Gas, Steam, Hot Water Heat .......................... Main Control Box
R21, 22 .............. Relays, Gas Heat, 100% OA ..................................... Furnace Sect.
R23 .................... Relay, Gas Heat, Modulating Valve ........................... Furnace Sect.
R24 .................... Relay, Gas Heat Alarm ............................................... Main Control Box
R26 .................... Relay, Occupied/Unoccupied .................................... Main Control Box
R27 .................... Relay, Exhaust Dampers ............................................ Main Control Box
R28 .................... Relay, Isolation Dampers ........................................... Main Control Box
R60-69 ............... Relays, Special ........................................................... Main Control Box
RAE .................... Return Air Enthalpy Sensor ....................................... Return Air Sect.
RAT .................... Return Air Temperature Sensor ................................. Return Air Sect.
REC1 ................. Receptacle, Main Box ................................................ Main Control Box
REC3 ................. Receptacle, Field Power, 115V .................................. Discharge Bulkhead
REC10-22 .......... Receptacles, Cabinet Section ................................... Cabinet Sections
S1 ....................... Switch, System On/Off, RPS Unit ............................. Main Control Box
S3 ....................... Switch, Furnace On/Off ............................................. Furnace Sect.
S4, 5 .................. Switches, AFD Bypasses ........................................... Main Control Box
S6 ....................... Switch, Return Fan Vanes Adjustment ...................... Main Control Box
S10-22 ............... Switches, Cabinet Section Lights ............................. Cabinet Sections
SAT .................... Supply Air Temperature Sensor ................................. Discharge Sect.
SB1 .................... Staging Board #1, Cooling ........................................ Main Control Box
SB2 .................... Staging Board #2, Heating ........................................ Main Control Box
SD1 .................... Smoke Detector, Supply Air ...................................... Discharge Sect.
SD2 .................... Smoke Detector, Return Air ....................................... Return Air Sect.
SPS1, 2 .............. Static Pressure Sensors, Duct or Building ................ Main Control Box
SPS5 .................. Static Pressure Sensor, Clogged Filter ..................... Filter Sect.
SPS6 .................. Static Pressure Sensor, Clogged Final Filter ............ Final Filter Sect.
SR1-3 ................ Sequence Relays, Electric Heat ................................ Electric Heat Sect.
T1 ....................... Transformer, Main Control ......................................... Main Control Box
T2 ....................... Transformer, Unit 24V ................................................ Main Control Box
T3 ....................... Transformer, Controller, 18V ...................................... Main Control Box
T4 ....................... Transformer, Exhaust Dampers ................................. Main Control Box
T5 ....................... Transformer, Electric Heat ......................................... Electric Heat Sect.
T7 ....................... Transformer, Gas Pilot Valve ...................................... Furnace Sect.
T8 ....................... Transformer, Gas Main Valve ..................................... Furnace Sect.
TB1 .................... Terminal Block, 115V, Field ........................................ Main/Cond. Ctrl Box
TB2 .................... Terminal Block, 24V, Field .......................................... Main/Cond. Ctrl Box
TB5 .................... Terminal Block, 115V, Factory ................................... Main Control Box
TB6 .................... Terminal Block, 115V/24V, Factory ............................ Main Control Box
TB7, 8 ................ Terminal Block, 24V, Factory ..................................... Main Control Box
TB10 .................. Terminal Block, Heating ............................................. Main Control Box
TB11 .................. Terminal Block, Heating ............................................. Electric Heat Sect.
TB12, 13 ............ Terminal Blocks, Electric Heat, Power ...................... Electric Heat Sect.
TB25 .................. Terminal Block, 115V, Factory ................................... Unit Split, Jct. Box
TB27, 28 ............ Terminal Blocks, 24V, Factory ................................... Unit Split, Jct. Box
TD9 .................... Time Delay, Supply Fan Part Winding ....................... Main Control Box
TD19 .................. Time Delays, Return Fan Part Winding ..................... Main Control Box
VM1 ................... Valve Motor #1, Heating ............................................ Heating Sect.
VM5 ................... Valve Motor #1, Cooling ............................................ Cooling Sect.
VV1 .................... Vent Valve, Gas Heat ................................................. Furnace Sect.
ZNT1 .................. Zone Temperature Sensor, Control ........................... Field Installed
ZNT2-5 .............. Zone Temperature Sensors, Special ......................... Field Installed

GENERAL NOTES

1.

2.

3.

4.

5.

6.

Field Wiring

Wiring in Remote Unit

Wiring Between Boxes

Shielded Wire Cable

Main Control Box

(Terminals)

Cond/Heat Control Box
(Terminals)

  7.

  8.

  9.

10.

11.

12.

200

Field Wiring Terminal

Remote Panel Terminal

Wire Connector

Plug-in Connector

Wire Number

Option Block

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание RoofPak RDS 802C

Страница 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Страница 2: ...1 Date January 1997 Installation Maintenance Data RoofPak Applied Rooftop Systems Air Handler RDS 800C 802C 1997 McQuay International L I S T E D L I S T E D C Artisan Technology Group Quality Instrum...

Страница 3: ...ntrol Circuit CAV ZTC Units 37 Typical Main Control Circuit CAV DTC Units 38 Typical Actuator Control Circuit 39 Typical Supply Return Fan Control Circuit 39 Typical Gas Furnace Control Circuit 40 Mod...

Страница 4: ...AV OM 108 Constant Air Volume Zone Temperature Control CAV ZTC OM 109 Constant Air Volume Discharge Temperature Control CAV DTC OM 110 When the equipment is received all items should be carefully chec...

Страница 5: ...ol Entrances Outside Return Air Dampers Exhaust Hood Main Control Panel Discharge Plenum Cooling Coil Outside Air Louvers Return Air Fan Supply Air Fan Filter Section Heat Section Natural Gas Oil Stea...

Страница 6: ...luded in the Wiring Diagrams section of this manual Figure 2 Control locations Return Air Economizer Filter Section Supply Fan Section Blow through Heat Section Blow through Coil Section Discharge Ple...

Страница 7: ...6 SPS1 SPS2 NB1 DHL ADI SB1 OBB OBA T1 FB10 FB20 M20 M10 OL20 OL10 FB8 TB8 TB7 DSI or PB1 TB10 TB5 NB2 TB1 TB2 TB2 MCB1 T2 Main control panel Supply Fan Section Main Control Panel Electric Heat Contro...

Страница 8: ...age 7 Electric heat control panel TB12 M43 M42 M41 FB43 FB42 FB41 M33 M32 M31 FB33 FB32 FB31 HL4 HL14 T5 SR1 SR2 SR3 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artis...

Страница 9: ...B or C 16 position 665422B 02 8 position 665422B 03 4 position PC5 6 Filter switch Turns on clogged filter light on status panel Auto Filter sections As required 05 5 w c 05 w c 654938B 01 12 5 1245...

Страница 10: ...allow flow of gas to pilot burner Normally Gas heating section N A N A N A 344884B 00 closed GV2 3 Main gas valves Open to allow flow of gas to main burner Normally Gas heating section N A N A N A See...

Страница 11: ...shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes Sharpedge...

Страница 12: ...box b Overhead obstructions shall be no less than 2 51 mm above the top of the unit c There shall be no overhead obstructions in the areas above the outside air and exhaust dampers that are farther t...

Страница 13: ...arts E and F are not required on units with no return shaft within the curb perimeter 9 Parts G and H are not required on units with no supply shaft within the curb perimeter 38 8 984 7 5 191 2 51 X I...

Страница 14: ...distance A Lift Only As Indicated Maximum recommended width for structural member is 5 127 mm to allow for adequate space for duct connections and electrical entry Rigging and Handling Lifting bracket...

Страница 15: ...ension Z i e A Z X Y Where Z Total unit length in inches refer to certified drawings for this dimension X Outdoor return air section length refer to Table 3 for this dimension If A 288 7315 mm 4 point...

Страница 16: ...e Unit Descrip tion section of this manual The duct static pressure sensing tap must be carefully located and installed Improper location or installation of the sensing tap will cause unsatisfactory o...

Страница 17: ...ence pressure LO tap on the roof Keep it away from the condenser fans walls or anything else that may cause turbulence Mount it high enough above the roof so that it is not affected by snow If the ref...

Страница 18: ...nimize This Dimension Note Drain line must not be run higher than this level A 8 203 mm Min or 2 x P Copper Tube one each end of coil See View A View A Drain Pan Static Pressure P in w c RDS units tha...

Страница 19: ...and there are no refrigerant leaks the system should be evacuated The use of a vacuum pump with a pumping capacity of approxi mately 3 cu ft min and the ability to reduce the vacuum in the unit to at...

Страница 20: ...each circuit Note The total operating charge per circuit should not exceed the pumpdown capacity per circuit specified by the condensing unit manufacturer Table 6 Approximate refrigerant charge per c...

Страница 21: ...a fin height of 39 991 mm A factory installed three way valve piping and motor actuator is available for hot water coils in a heating only section see Figure 13 When no factory piping or valve is incl...

Страница 22: ...erally the vacuum breaker is to be connected between the coil inlet and the return main However if the system has a flooded return main the vacuum breaker should be open to the atmosphere and the trap...

Страница 23: ...unit and vestibule with silicone sealant along top and sides as shown Note Any holes cut in the floor of the unit must be sealed to prevent water leakage Figure 16d Step 3 1 Assemble side panels A an...

Страница 24: ...s through a 90 degree angle to bring the economizer dampers from full open to full close Mechanical stops have been placed in the crankarm mounting bracket Do not remove stops If the crankarm is drive...

Страница 25: ...tact the adjoining blade The blades will lock up if they are closed so far the seal goes over center 75 Figure 19 Intake hood damper 0 to 30 outside air These dampers are intended to remain at a fixed...

Страница 26: ...atherproof opera tion After the unit has been set in place all door gaskets should be inspected for shipping damage and replaced if necessary It is recommended the unit be protected from overhead runo...

Страница 27: ...uits can penetrate the cabinet bottom base frame or through the hinge and latch cap without interfering with the access panels Note All holes cut into the unit must be sealed to prevent water leakage...

Страница 28: ...on the unit If side entrance is the only option a drilling location is provided The drilling dimen sions must be followed exactly to prevent damage to the control panel The dimensions provided are the...

Страница 29: ...r death Connect only low voltage NEC Class II circuits to termi nal blocks TB2 and TB7 Reinstall and secure all protective deadfront panels when the wiring installation is complete Most field control...

Страница 30: ...sure plug in the louvered fresh air intake area Replace the closure plug after removing lock down bolt All four bolts on each fan assembly must be removed Adjustment of spring mounts Each spring mount...

Страница 31: ...After the spring mounts have been adjusted for level opera tion the thrust restraints should be checked With the fan off the adjustment nuts should be set so the spring is slightly compressed against...

Страница 32: ...located next to each spring isolator These snubbers will allow free movement of the fan assem blies during normal operation because normal operation will not cause fan movements that exceed 25 6 mm H...

Страница 33: ...n the ADI board If DH2 8 does not energize the controller will assume the fans did not start It will then shut down the unit and generate an alarm During the Recirculate operating state the outside ai...

Страница 34: ...energizing relay R20 and opening its contacts in line 610 As a result the flame safeguard control is de energized all gas valves close the combustion air blower motor stops and gas valve actuator VM1...

Страница 35: ...ensor Discharge Bulkhead OBA Output Board A Standard Main Control Box OBB Output Board B Cooling Main Control Box OBC Output Board C Heating Main Control Box OL9 10 Overload Relays Supply Fan Main Con...

Страница 36: ...IM 178 Page 35 Typical Power Circuit Typical Compressor Staging Outputs Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 37: ...Page 36 IM 178 Typical Main Control Circuit VAV Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 38: ...IM 178 Page 37 Typical Main Control Circuit CAV ZTC Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 39: ...Page 38 IM 178 Typical Main Control Circuit CAV DTC Units Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 40: ...IM 178 Page 39 Typical Actuator Control Circuit Typical Supply Return Fan Control Circuit Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 41: ...o indicate operation Low fire start is provided by relay R23 The relay drives the gas valve actuator VM1 to the minimum firing rate position whenever the flame is not on and holds it there until the f...

Страница 42: ...IM 178 Page 41 Typical Electric Heat Control Circuit Multistage Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 43: ...t is on when all phase voltages are within specified limits The phase voltage monitor is located on the load side of the power block with a set of contacts wired to the 115 volt control circuit to shu...

Страница 44: ...eating valve will close If the freezestat closes again the heating valve will open and the 10 minute timer will reset The unit will remain shut down until the Freeze Stat Fail alarm is manually cleare...

Страница 45: ...ontrols on both the supply and return fan it is important that both actuators have exactly 180 degree rotation to assure proper tracking of the two actuators NOTICE Inlet vanes must not be adjusted to...

Страница 46: ...To Open 20 Closed Open 2 78 View 1 30 Wheel 800C 802C View 2 40 Wheel 802C Closed Open 60 A B X 3 00 20 Wheel 800C 2 80 24 Wheel 802C 180 CW To Open X 24 Closed Open Adjustable 11 8 28 mm slot Figure...

Страница 47: ...el 7 If unit is curb mounted verify that the curb is properly flashed to prevent water leakage 8 Before attempting to operate the unit review the control layout description to become familiar with the...

Страница 48: ...ing system switch S1 Economizer Start up Improper adjustment may damage the dampers Assure proper damper adjustment When an economizer is ordered without an actuator the linkage requires a 3 14 linear...

Страница 49: ...re than five full turns for A belts or six full turns for B belts Adjust both halves of two groove sheaves by the same number of turns from closed to ensure that both grooves have the same pitch diame...

Страница 50: ...isfac tory locking of the sheave If locking screws A are removed by accident and the gap is lost screw the outer locking ring down until it touches the inner locking ring Then back off the outer ring...

Страница 51: ...e operating schedule as required keypad menus 25 and 26 15 Place the unit into the Calibrate mode by selecting it from keypad menu 11 Control Mode Calibrate will automatically zero all pressure sensor...

Страница 52: ..._______ 14 Htg Control VAV CAV DTC Set Point ____ F ___________ Max OAT ____ F ___________ Programs ART1 ART2 ART3 Min Spt ____ F ___________ ART4 ART6 and ART8 Max Spt ____ F ___________ Reset No Res...

Страница 53: ...ime ____ Sec ___________ and ART6 Mod Lim ____ WC ___________ Wait Time ____ Sec ___________ Max Step ____ Sec ___________ 20 Fan Balance VAV with fan Balance Off ___________ tracking control On Set M...

Страница 54: ..._______ Sun hr mn hr mn ___________ Mon hr mn hr mn ___________ Tue hr mn hr mn ___________ Wed hr mn hr mn ___________ Thu hr mn hr mn ___________ Fri hr mn hr mn ___________ Sat hr mn hr mn ________...

Страница 55: ...n ___________ 28 Service Mode Normal ___________ Shutdown Timers Normal ___________ Fast Space Sensor No ___________ Yes OAT Local ___________ Remote Duct Sensor 2 No ___________ Yes Alarm Out Blink _...

Страница 56: ...and control voltages 8 Check the running amperage of all motors 9 Check all operating temperatures and pressures 10 Check and adjust all temperature and pressure controls as needed 11 Check and adjus...

Страница 57: ...o assure that they have not loos ened If this is not done severe equipment damage could occur Using Table 16 check the tightness of all setscrews with a torque wrench Note that if the return fan beari...

Страница 58: ...5 25 Funnel Wheel 18 9 31 9 31 Wheel Funnel C L Fan Winterizing Water Coils Coil freeze up can be caused by such things as air stratifica tion and failure of outdoor dampers and or preheat coils Routi...

Страница 59: ...your nearest McQuay representa tive The order should include the component s part number and description and the model and serial numbers of the unit involved If it is determined that the failure of...

Страница 60: ...f all other warranties There is no implied warranty of merchantability or fitness for a particular purpose In no event and under no circumstances shall the Company be liable for incidental or conseque...

Страница 61: ...ard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330 Printed on recycled paper containing at least 10 post consumer recycled material Artisan Technology Group Quality Instrumentation Guaranteed 888...

Страница 62: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Отзывы: