Description Default
Range
Unit
Ft/Lb
SI
Oil Press Differential
35 PSI
250 kPa
0-60 PSI / 0 to 415 kPa
Low Oil Level Delay
120 sec
10 to 180 sec
High Discharge Temperat.
230
°
F
110 °C
150 to 230 °F / 65 to 110 °C
High Lift Pressure Delay
5 sec
0 to 30 sec
Low Pressure Ratio Delay
90 sec
30-300 sec
Start Time Limit
60 sec
20 to 180 sec
Evaporator Water Freeze
36
°
F
2,2 °C
See section 0
Evaporator Flow Proof
15 sec
5 to 15 sec
Recirculate Timeout
3 min
1 to 10 min
Low Ambient Lockout
Enable
Disable Disable,
Enable
Low Ambient Lockout
55
°
F
12°C
See section 0
The following set points exist individually for each circuit:
Description Default
Range
PW
Ft/Lb
SI
Circuit mode
Enable
Disable, enable, test
S
Compressor Size
To be Verified
M
Capacity Control
Auto
Auto, Manual
S
Manual Capacity
See note 1 below table
0 to 100%
S
Clear Cycle Timers
No
No, yes
M
EXV control
Auto
Auto, manual
S
EXV position
See note 2 below table
0% to 100%
S
Oil Sump Check
Enable
Enable, Disable
S
Service Pumpdown
No
No,Yes
S
Evap pressure offset
0PSI
0kPa
-14.5 to 14.5 PSI /-100 to 100 kPa
S
Cond pressure offset
0PSI
0kPa
-14.5 to 14.5 PSI /-100 to 100 kPa
S
Oil pressure offset
0PSI
0kPa
-14.5 to 14.5 PSI /-100 to 100 kPa
S
Suction temp offset
0°F
0°C
-5.0 to 5.0 deg
S
Discharge temp offset
0°F
0°C
-5.0 to 5.0 deg
S
Fans
Fan VFD enable
On
Off, On
M
Number of fans
5
5 to 12
M
Saturated Condenser Temp
Target Min
90 °F
32°C
80.0-110.0
o
F / 26.0 to 43.0 °C
M
Saturated Condenser Temp
Target Max
110 °F
43°C
90.0-120.0
o
F / 32.0 to 50 °C
M
Fan Stage Up Deadband 0
5 °F
2.5 °C
1-20
o
F / 1-10 °C
M
Fan Stage Up Deadband 1
5 °F
2.5 °C
1-20
o
F / 1-10 °C
M
Fan Stage Up Deadband 2
8 °F
4 °C
1-20
o
F / 1-10 °C
M
Fan Stage Up Deadband 3
10 °F
5 °C
1-20
o
F / 1-10 °C
M
Fan Stage Up Deadband 4
8 °F
4 °C
1-20
o
F / 1-10 °C
M
Fan Stage Up Deadband 5
8 °F
4 °C
1-20
o
F / 1-10 °C
M
Fan Stage Down Deadband 2
8 °F
4 °C
1-25
o
F / 1-13 °C
M
Fan Stage Down Deadband 3
7 °F
3.5 °C
1-25
o
F / 1-13 °C
M
Fan Stage Down Deadband 4
6 °F
3 °C
1-25
o
F / 1-13 °C
M
Fan Stage Down Deadband 5
5 °F
2.5 °C
1-25
o
F / 1-13 °C
M
Fan Stage Down Deadband 6
5 °F
2.5 °C
1-25
o
F / 1-13 °C
M
VFD Max Speed
100%
90 to 110%
M
VFD Min Speed
25%
20 to 60%
M
Note 1 – This value will follow the actual capacity while Capacity Control = Auto.
Note 2 – This value will follow the actual EXV position while EXV Control = Auto.