![McQuay AWS Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/mcquay/aws/aws_operating-manual_1756102044.webp)
44
KOMAC00607-09EN
Reset:
This alarm can be cleared manually via the keypad, but only if the sensor
is back in range.
Oil Pressure Sensor Fault
Alarm description (as shown on screen):
OilPressSensFault N
Trigger:
Sensor shorted or open
Action Taken:
Normal shutdown of circuit
Reset:
This alarm can be cleared manually via the keypad, but only if the sensor
is back in range.
Suction Temperature Sensor Fault
Alarm description (as shown on screen):
SuctTempSensFault N
Trigger:
Sensor shorted or open
Action Taken:
Normal shutdown of circuit
Reset:
This alarm can be cleared manually via the keypad, but only if the sensor
is back in range.
Discharge Temperature Sensor Fault
Alarm description (as shown on screen):
DiscTempSensFault N
Trigger:
Sensor shorted or open
Action Taken:
Normal shutdown of circuit
Reset:
This alarm can be cleared manually via the keypad, but only if the sensor
is back in range.
Motor Temperature Sensor Fault
Alarm description (as shown on screen):
MotorTempSensFault N
Trigger:
Sensor shorted or open
Action Taken:
Rapid stop circuit
Reset:
This alarm can be cleared manually via the keypad, but only if the sensor
is back in range.
Circuit Events
The following events limit operation of the circuit in some way as described in the
Action Taken column. The occurrence of a circuit event only affects the circuit on which
it occurred. Circuit events are logged in the event log on the unit controller.
Low Evaporator Pressure - Hold
Event description (as shown on screen):
EvapPress Low Hold N
Trigger:
This event is not enabled until the circuit startup is complete and the unit
mode is Cool. Then, while running, if evaporator pressure <= Low Evaporator
Pressure Hold set point the event is triggered. The event is not to be triggered for
90 seconds following the capacity change of the compressor from 50% to 60%.
Action Taken:
Inhibit loading.
Reset:
While still running, the event will be reset if evaporator pressure > (Low
Evaporator Pressure Hold SP + 2psi). The event is also reset if the unit mode is
switched to Ice, or the circuit is no longer in the run state.
Low Evaporator Pressure - Unload
Event description (as shown on screen):
EvapPressLowUnload N
Trigger:
This event is not enabled until the circuit startup is complete and the unit
mode is Cool. Then, while running, if evaporator pressure <= Low Evaporator
Pressure Unload set point the event is triggered. The event is not to be triggered
for 90 seconds following the capacity change of the compressor from 50% to
60%.