KOMAC00607-09EN
17
Setpoints
The following parameters are remembered during power off, are factory set to the
Default
value, and can be adjusted to any value in the
Range
column.
Read and write access to these set points is determined by the Global HMI (Human Machine
Interface) Standard Specification.
Table 1, Setpoint Value and Range
Description Default
Range
Unit
Ft/Lb
SI
Manufacturing Location
Not Selected
Not Selected, Europe, USA
Unit Enable
OFF
OFF, ON
Unit Status after Power
Failure
OFF OFF,
ON
Control source
Local
Local, Network
Available Modes
Cool
COOL
COOL/w GLYCOL
COOL/ICE w GLYCOL
ICE
TEST
Cool LWT 1
44
°
F
7 °C
See section 0
Cool LWT 2
44
°
F
7 °C
See section 0
Ice LWT
25
°
F
-4 °C
20 to 38
°
F / -8 to 4 °C
Startup Delta T
5
°
F
2,7 °C
0 to 10
°
F / 0 to 5 °C
Shut Down Delta T
2.7
°
F
1.5 °C
0 to 3
°
F / 0 to 1,7 °C
Stage Up Delta T (between
compressors)
2
°
F
1 °C
0 to 3
°
F / 0 to 1,7 °C
Stage Down Delta T
(between compressors)
1
°
F
0,5 °C
0 to 3
°
F / 0 to 1,7 °C
Max Pulldown
3
°
F/min
1,7
°C/min
0.5-5.0
°
F /min / 0,3 to 2,7 °C/min
Evap Recirc Timer
30
0 to 300 seconds
Evap Control
#1 Only
#1 Only, #2 Only, Auto,
#1 Primary, #2 Primary
LWT Reset Type
NONE
NONE, RETURN, 4-20mA, OAT
Max Reset
10
°
F
5 °C
0 to 20
°
F / 0 to 10 °C
Start Reset Delta T
10
°
F
5 °C
0 to 20
°
F / 0 to 10 °C
Start Reset OAT
75°F
23.8°C
50°F - 85°F / 10.0 – 29.4°C
Max Reset OAT
60°F
15.5°C
50°F - 85°F / 10.0 – 29.4°C
Soft Load
Off
Off, On
Begin Capacity Limit
40%
20-100%
Soft Load Ramp
20 min
1-60 minutes
Demand Limit
Off
Off, On
Current Limit
Off
Off, On
Current @ 20mA
800 Amp
0 to 2000 Amp = 4 to 20 mA
Current limit Set Point
800 Amp
0 to 2000 Amp
# of Circuits
2
2-3-4
Ice Time Delay
12
1-23 hours
Continued next page.