Reset:
Auto reset when sensor is back in range.
Unit Power Restore
Event description (as shown on screen):
Unit Power Restore
Trigger:
Unit controller is powered up.
Action Taken:
none
Reset:
none
External Event
Alarm description
(as shown on screen)
: External Event
Trigger:
External Alarm/Event input is open for at least 5 seconds and external
fault is configured as an event.
Action Taken:
None
Reset:
Auto clear when digital input is closed.
Low Ambient Lockout
Alarm description
(as shown on screen):
Low Ambient Lockout
Trigger:
The OAT drops below the low ambient lockout set point and low
ambient lockout is enabled.
Action Taken:
Normal shutdown of all running circuits.
Reset:
The lockout will clear when OAT rises to the lockout set point plus 2.5°C,
or when low ambient lockout is disabled.
Circuit Stop Alarms
All circuit stop alarms require shutdown of the circuit on which they occur. Rapid stop
alarms do not do a pumpdown before shutting off. All other alarms will do a
pumpdown.
When one or more circuit alarms are active and no unit alarms are active, the alarm
output will be switched on and off on 5 second intervals.
Alarm descriptions apply to all circuits, the circuit number is represented by ‘N’ in the
description.
Phase Volts Loss/GFP Fault
Alarm description (as shown on screen):
PVM/GFP Fault N
Trigger:
PVM input is low and PVM set point = Multi Point
Action Taken:
Rapid stop circuits
Reset:
Auto reset when PVM input is high or PVM set point does not equal multi
point for at least 5 seconds.
Low Evaporator Pressure
Alarm description (as shown on screen):
Evap Press Low N
Trigger:
[Freezestat trip AND Circuit State = Run] OR Evaporator Press < -10 psi
Freezestat logic allows the circuit to run for varying times at low pressures. The
lower the pressure, the shorter the time the compressor can run. This time is
calculated as follows:
Freeze error
= Low Evaporator Pressure Unload – Evaporator Pressure
Freeze time
= 70 – 6.25 x freeze error, limited to a range of 20-70 seconds
When the evaporator pressure goes below the Low Evaporator Pressure Unload set
point, a timer starts. If this timer exceeds the freeze time, then a freezestat trip
occurs. If the evaporator pressure rises to the unload set point or higher, and the
freeze time has not been exceeded, the timer will reset.
The alarm cannot trigger if the evaporator pressure sensor fault is active.
Action Taken:
Rapid stop circuit