86
AGZ 026B through 130B
IOMM AGZ-5
Unit Mode settings can be:
1. COOL, normal setting used with chilled water air-condition applications.
2. COOL w/GLYCOL, used with low temperature glycol applications. It allows a
lower LWT setpoint to be used.
3. ICE w/GLYCOL, used with ice storage systems, allows changing from chilled
glycol operation to lower temperature ICE operation. In ICE, the unit runs at full
load until the ICE setpoint is reached, at which time the unit shuts off. A three-
position switch wired to terminals #28 and #38 initiates the change from glycol
cooling to making ice. (See wiring diagram on page 50.)
4. TEST, for use by service technician for certain test procedures.
SET UNIT SPs (2)
Available Modes
=COOL w/Glycol
Set w/ FP Switch Off
Available Modes settings can be COOL, COOL w/Glycol, ICE w/Glycol, or TEST as
selected from the available modes imbedded in the menu. The 4
th
line is a reminder
that the ON/OFF switch on the front panel (FP) must be in the OFF position before the
MODE can be changed. This prevents a mode change while the unit is operating.
SET UNIT SPs (3)
Evap LWT =
XX.X
°°°°
F
Ice LWT =
XX.X
°°°°
F
SET UNIT SPs (4)
EvapDeltaT= XX.X
°°°°
F
StartDelta= XX.X
°°°°
F
Stop Delta = XX.X
°°°°
F
See the Compressor Control section beginning on page 61 for explanation.
SET UNIT SPs
(5)
Max Pulldn=X.X
°°°°
F/min
Evap Recirc=XXX sec
LowAmbLock= XX.X
°°°°
F
SET UNIT SPs
(6)
Demand Limit=No
Multipoint Power=No
SET UNIT SPs (7)
CLOCK
dd/mmm/yyyy
hh:mm:weekday