88
AGZ 026B through 130B
IOMM AGZ-5
SET UNIT SPs (15)
ENTER PASSWORD XXXX
Active Password
Level:None
SET COMP SETPOINTS
SET COMP SPs (1)
# of Compressors =X
Stop-Start
=XXmin
Start-Start =XXmin
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a
compressor after it has
stopped
. Start-Start is the time required before starting a
compressor after the last time it has
started
. It is recommended that these default
values not be changed.
SET COMP SPs (2)
InterStageUp=XXXsec
InterStageDn=XXXsec
Clear Cycle Tmrs =no
InterStageUp is the time delay since the last stage change before a compressor can
stage on.
InterStageDn is the time delay since the last stage change before a compressor can
stage off normally (not by an alarm).
SET LIMIT ALARMS
SET ALARM LMTS (1)
LowEvPrHold=XXXpsi
LowEvPrUnld=XXXpsi
The LowEvPrHold and LowEvPrUnld have the same default value of 59 psi. If two
compressors are running, the LowEvPrUnld is in effect and the lag compressor will be
shut off to unload the unit. If one compressor is running, the LowEvPrHold is in effect
and the lag compressor is prevented from starting, thereby holding the unit capacity.
SET ALARM LMTS (2)
Evap Freeze= XX.X
°°°°
F
EvapFlowProof=XXXsec
Evap Freeze (the unit freeze protection shutdown) is actually a stop alarm and shuts off
the unit when the LWT reaches 36
°
F. It is cleared by going to the CLEAR ALARM
menu in the ACTIVE ALARM hierarchy.
EvapFlowProof is a time delay on the flow switch trip that reduces nuisance low flow
trips. The default setting is 5 seconds.