BAS Limit
The maximum unit capacity can be limited by a BAS signal. This function is only
enabled if the unit control source is set to network. The maximum unit capacity stage
is based on the BAS limit value received from the BAS, and is determined as shown in
the graphs in the previous section.
Maximum LWT Rate
The maximum rate at which the leaving water temperature can drop is limited at all
times by the Maximum Rate setpoint. If the rate exceeds this setpoint, no more
compressors will be started until the pulldown rate is less than the setpoint.
Pumpdown
When a circuit reaches a condition where it needs to shut down normally, a pumpdown
cycle will be performed. All but the lowest numbered running compressor will shut off.
During pumpdown, the hot gas bypass and liquid line valves are closed, while a
compressor continues to run. The pumpdown is complete when the evaporator
pressure is less than the low evaporator pressure unload setpoint, less 15 psi, or the
circuit has been in the pumpdown state for 60 seconds.
Condenser Fan Control
Stage Up Compensation
In order to create a smoother transition when another fan is staged on, the VFD
compensates by slowing down initially. This is accomplished by adding the new fan
stage up deadband to the VFD target. The higher target causes the VFD logic to
decrease fan speed. Then, every 10 seconds, 0.5 degree F is subtracted from the VFD
target until it is equal to the saturated condenser temperature target setpoint. This will
allow the VFD to slowly bring the saturated condenser temperature back down.
Fantrol
Condenser Fans Staging is based on condenser pressure as selected by Fan Stage On &
Off setpoints. Fans 1, 3, 5, and 7 are for circuit 1, and fans 2, 4, 6, and 8 are for circuit
2. Fans 1 and 2 start with the first compressor on the respective circuit when the
ambient temperature is greater than 75
°
F. Below 75
°
F, these fans start when the
condenser pressure gets up to the stage on setpoint. The compressor must be running in
order to run any fans.