33
Electrical Data - Standard Ambient
Table 19, AGZ 026BM/BS – 070BM/BS, Electrical Data, Single Point
(105°F & below)
Power Supply
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
208
133
3
1/0
150
150
230
126
3
#1
150
150
380
80
3
#4
90
90
460
68
3
#4
80
80
026B
575
52
3
#6
60
60
208
146
3
1/0
175
175
230
143
3
1/0
175
175
380
88
3
#3
100
100
460
74
3
#4
80
90
030B
575
58
3
#6
70
70
208
158
3
2/0
175
175
230
150
3
1/0
175
175
380
96
3
#3
110
110
460
79
3
#4
90
90
035B
575
64
3
#6
70
70
208
167
3
2/0
200
200
230
167
3
2/0
200
200
380
113
3
#2
125
125
460
81
3
#4
90
90
040B
575
70
3
#4
80
80
208
184
3
3/0
225
225
230
184
3
3/0
225
225
380
121
3
#1
125
125
460
94
3
#3
110
110
045B
575
78
3
#4
90
90
208
199
3
3/0
225
225
230
199
3
3/0
225
225
380
127
3
#1
150
150
460
104
3
#2
125
125
050B
575
86
3
#3
100
100
208
221
3
4/0
250
250
230
214
3
4/0
250
250
380
145
3
1/0
175
175
460
108
3
#2
125
125
055B
575
96
3
#3
110
110
208
248
3
250
300
300
230
228
3
4/0
250
250
380
156
3
2/0
175
175
460
112
3
#2
150
150
060B
575
105
3
#2
125
125
208
281
3
300
350
350
230
281
3
300
350
350
380
162
3
2/0
200
200
460
124
3
#1
150
150
065B
575
109
3
#2
125
125
208
301
3
350
350
350
230
301
3
350
350
350
380
168
3
2/0
200
200
460
130
3
#1
150
150
070B
575
112
3
#2
125
125
NOTES:
1.
Units operating in ambient temperatures of 95
°
F (35
°
C) and above must use the
Maximum Fuse or HACR Breaker size.
2.
All Electrical Data notes are on page 49.
3.