46
AGZ 026B through 130B
IOMM AGZ-5
Table 32, AGZ 075BB/BH – 130BB/BH, Electrical Data, Single Point
(Above 105°F)
Power Supply
Max. Fuse
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Or HACR
Breaker
Size
208
378
6
250
450
450
230
362
6
4/0
400
400
380
194
3
3/0
225
225
460
187
3
3/0
225
225
075B
575
145
3
1/0
175
175
208
398
6
250
450
450
230
382
6
250
450
450
380
234
3
250
250
250
460
200
3
4/0
225
225
085B
575
151
3
1/0
175
175
208
416
6
300
500
500
230
401
6
350
450
450
380
270
3
300
300
300
460
211
3
4/0
250
250
090B
575
157
3
2/0
175
175
208
522
6
400
600
600
230
462
6
350
500
500
380
273
3
300
300
300
460
230
3
4/0
250
250
100B
575
187
3
3/0
200
200
208
612
6 - (2)
350
700
700
230
526
6 - (2)
300
600
600
380
307
3
350
350
350
460
263
3
300
300
300
110B
575
211
3
4/0
225
225
208
612
6 - (2)
350
700
700
230
571
6 - (2)
350
600
600
380
352
6 - (2)
4/0
400
400
460
286
3
350
300
300
120B
575
219
3
4/0
250
250
208
613
6 - (2)
350
700
700
230
613
6 - (2)
350
700
700
380
393
6
250
450
450
460
307
3
350
350
350
130B
575
228
3
250
250
250
NOTES:
1.
Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum
Fuse or HACR Breaker size.
2.
All Electrical Data notes are on page 49.
3.
(2) in column with wire qty. indicates that two conduits are required.
4.
Conduit hubs are not supplied.