IOMM AGZ-5
AGZ 026B through 130B
57
Setpoints
The setpoints shown in Table 39 are retained by battery-back-up and remembered
during power off, are factory set to the
Default
value, and can be adjusted within the
values shown in
Range
.
The PW (password) column indicates the password. Passwords are as follows:
O = Operator =0100
M = Manager=2001
Table 39, Setpoints
Description Default
Range PW
Unit Enable
OFF
OFF, ON
O
Unit Mode
COOL
COOL, COOL w/Glycol, ICE w/Glycol, TEST
O
Control source
DIGITAL
INPUT
KEYPAD, BAS, DIGITAL INPUT
O
Available Modes
COOL
COOL, COOL w/GLYCOL, COOL/ICE w/GLYCOL,
ICE w/GLYCOL. TEST
M
Display Units
Language
Protocol
Modbus
BACnet, LonWorks, Modbus
M
Ident number (Modbus only)
001
001-999
M
Baud rate (Modbus only)
9600
1200,2400,4800,9600,19200
M
Cool LWT
44. 0
°
F
20.0(40.0) to 60.0
°
F
O
Ice LWT
40. 0
°
F
20.0 to 40.0
°
F
O
Evap Delta T
10. 0
°
F 6.0
to
16.0
°
F
O
Startup Delta T
5.0
°
F 1.0
to
10.0
°
F
O
Stop Delta T
0.5
°
F 0.5
to
3.0
°
F
O
Max Pulldown Rate
1.0
°
F
0.5 to 5.0
°
F
M
Evap Recirculate Timer
30
15 to 300 sec
M
Low Ambient Lockout
35
°
F
–2(35) to 60
°
F
M
Demand Limit
No
No,Yes
M
* Multipoint Power
No
No,Yes
M
Compressor
* Number of Compressors
4
4,6
M
Stage Up Delay
120
90 to 240 sec
M
Stage Down Delay
30
20 to 60 sec
M
Start-Start
15 min
10 to 60 min
M
Stop-Start
5 min
3 to 20 min
M
Clear Cycle Timers
No
No,Yes
M
Alarms
Low Evap Pressure-Hold
59 psi
31 to 65 psi
M
Low Evap Pressure-Unload
59 psi
31 to 65 psi
M
High Condenser Stage Down
370 psi
365 to 380 psi
M
High Condenser Pressure
385 psi
385 to 390 psi
M
Evaporator Water Freeze
38.0
°
F 18(37)
to
42
°
F
M
* Phase Voltage Protection
No
No,Yes
M
* Ground Fault Protection
No
No,Yes
M
Evap Flow Proof
5 sec
3 to 30 sec
M
Condenser Fans
VFD Enable
No
No,Yes
M
* Number of Fans
4
4,6,8
M
Stage Up 2 Deadband
8
1 to 20
o
F M
Stage Up 3 Deadband
10
1 to 20
o
F M
Stage Up 4 Deadband
12
1 to 20
o
F M
Stage Down 0 Deadband
15
1 to 20
o
F M
Stage Down 1 Deadband
7
1 to 20
o
F M
Stage Down 2 Deadband
6
1 to 20
o
F M
Stage Down 3 Deadband
5
1 to 20
o
F M
VFD Max Speed
100%
90 to 110%
M
VFD Min Speed
25%
25 to 60%
M
Sat Condenser Temp Target
100
90 to 130
°
F
M
Forced Fan 1
1
1 to # Fans Per Circuit
M
Forced Fan 2
2
1 to # Fans Per Circuit
M
Forced Fan 3
3
1 to # Fans Per Circuit
M
(*) These items are factory set prior to shipment.