12. Before purging or releasing hot water from the chiller unit, allow sufficient time for the water
to cool down first. Water temperature of 40 to 50°C can cause injury to the body. Remember
also that the hot water will be under a higher pressure and sudden opening of drain valves
may cause spitting out of hot water.
External boiler installation
In some instances, the heating capacity of the mini chiller unit is not sufficient for an
application. Therefore, to supplement the heating capacity, two methods can be used:
1. Electric heater
1-phase or 3-phase electric heaters can be installed into the fan coil units or into the duct
work itself to generate the extra heating capacity required. However, proper installation
of the heaters must be done to prevent risk of fire. Due to the high amperage of the
heaters, suitable cable size must be used. The heaters must interlock with the fan coil
blowers whereby the heaters will not switch on as long as the blower is off. This is to
prevent overheating. Thermostats must also be installed near the heaters to cut-off the
heaters when the temperature gets too hot.
Generally, heaters are easy and convenient to use. However, the operating cost of the
electricity used is high.
2. Hot water boiler (diesel fired, fuel oil fired or gas fired)
Boilers can handle larger heating loads with a lower operating cost when compared with heaters.
With proper installation and maintenance, boilers can be made to run with high efficiencies.
Nevertheless, the operation of the boiler is more complex. Safety requirements are higher. The
safe operation of boilers is beyond the scope of this manual. Please refer to the boiler
manufacturers for more details and information.
There are several methods available to run the piping between the boiler and the mini
chiller unit, together with the fan coil units. This will depend on the design requirements of
a particular system. Only 2 common methods will be discussed here:
a. 2-pipe system
In this method, the boiler is connected with a cooling only mini chiller unit via a 3-way
positioning valve which is then piped to the fan coil units.
All the fan coil units must required either cooling or heating loading. It is not possible
to have some fan coils in cooling and some in heating.
However, the boiler will take up all the heating load which cannot be supplied by the
mini chiller unit.
Section 10
Page 118
Содержание AC 40A
Страница 1: ...AM MAC ...
Страница 153: ...Appendix 1 ...
Страница 154: ...Appendix 2 Appendix 2 ...
Страница 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Страница 158: ......
Страница 159: ...Water Capacity Graph Appendix 5 2 ...
Страница 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Страница 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Страница 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Страница 168: ...Appendix 8 Appendix 8 ...
Страница 169: ...Appendix 8 1 ...
Страница 170: ...Appendix 8 2 ...
Страница 171: ...Appendix 8 3 ...
Страница 172: ...Appendix 8 4 ...
Страница 173: ...Appendix 8 5 Appendix 8 5 ...
Страница 174: ...Appendix 8 6 Appendix 8 6 ...
Страница 175: ...Appendix 8 7 Appendix 8 7 ...
Страница 176: ...Appendix 9 ...
Страница 178: ...Appendix 11 1 Appendix 11 1 ...
Страница 179: ...Appendix 11 2 Appendix 11 2 ...
Страница 180: ...Appendix 13 ...
Страница 181: ...Appendix 13 1 ...
Страница 182: ...Appendix 14 Appendix 14 ...
Страница 183: ...Appendix 15 1 Appendix 15 1 ...
Страница 186: ...Appendix 17 Appendix 17 ...
Страница 187: ...Appendix 18 ...
Страница 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Страница 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...