Section 6: Water Storage Tank and Expansion
Tank
It has been mentioned in the
Introduction
that there is a water buffer storage tank inside the
mini chiller unit [for series A and series B versions]. The capacity of the tank is:
Model
Capacity/litres
AC 40A
AC 50A
AC 58A
32
AC 75B
AC100B
AC125B
150
The function of having this tank is to create a volume of water large enough to prevent short
cycling of the compressor, i.e. to prevent the compressor from switching ON/OFF too frequently.
This will usually happen during low load conditions, e.g. during night time, when the indoor fan
coil units may switch off by the action of the room thermostat. As a result, only one or two fan coil
units will be running while the larger capacity chiller unit continues to operate.
What is the effect of having the compressor switching ON/OFF too frequently? The main problem
is overheating of the compressor motor winding. The winding will not get sufficient cooling from
the refrigerant flow, and also there may be insufficient oil return which causes insufficient
lubrication.
Therefore, it is vital that a proper calculation of the total system water volume to be made to
determine if the chiller can operate safely.
The formula to calculate the minimum water volume is as follows:
V
min
=
860 * kW * Compressor OFF time
∆
T * 60 * No. of load steps (or No. of compressors)
Units: Conversion:
V
min
litre
1 kW = 3412 Btu/hr
OFF time minutes
∆
T deg. C
Example:
A mini chiller (series A) has a cooling capacity of 40,000 Btu/hr (11.72 kW).
The mini chiller controller has been programmed to operate with a minimum
compressor run time of 3 minutes and an off time of 4 minutes (i.e. a minimum
cyle of 7 minutes.)
Section 6
Page 87
Содержание AC 40A
Страница 1: ...AM MAC ...
Страница 153: ...Appendix 1 ...
Страница 154: ...Appendix 2 Appendix 2 ...
Страница 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Страница 158: ......
Страница 159: ...Water Capacity Graph Appendix 5 2 ...
Страница 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Страница 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Страница 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Страница 168: ...Appendix 8 Appendix 8 ...
Страница 169: ...Appendix 8 1 ...
Страница 170: ...Appendix 8 2 ...
Страница 171: ...Appendix 8 3 ...
Страница 172: ...Appendix 8 4 ...
Страница 173: ...Appendix 8 5 Appendix 8 5 ...
Страница 174: ...Appendix 8 6 Appendix 8 6 ...
Страница 175: ...Appendix 8 7 Appendix 8 7 ...
Страница 176: ...Appendix 9 ...
Страница 178: ...Appendix 11 1 Appendix 11 1 ...
Страница 179: ...Appendix 11 2 Appendix 11 2 ...
Страница 180: ...Appendix 13 ...
Страница 181: ...Appendix 13 1 ...
Страница 182: ...Appendix 14 Appendix 14 ...
Страница 183: ...Appendix 15 1 Appendix 15 1 ...
Страница 186: ...Appendix 17 Appendix 17 ...
Страница 187: ...Appendix 18 ...
Страница 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Страница 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...