During installation, it is important to ensure that the sensing bulb is in touch with the flowing
stream of water. If the thermometer is installed too "high" up the connecting socket, the
bulb will measure the temperature of stagnant water in the socket.
thermometer too
high up
stagnant water
Thermometer bulb
measuring correct
water flow
temperature
CORRECT INCORRECT
Section 3
Page 57
Содержание AC 40A
Страница 1: ...AM MAC ...
Страница 153: ...Appendix 1 ...
Страница 154: ...Appendix 2 Appendix 2 ...
Страница 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Страница 158: ......
Страница 159: ...Water Capacity Graph Appendix 5 2 ...
Страница 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Страница 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Страница 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Страница 168: ...Appendix 8 Appendix 8 ...
Страница 169: ...Appendix 8 1 ...
Страница 170: ...Appendix 8 2 ...
Страница 171: ...Appendix 8 3 ...
Страница 172: ...Appendix 8 4 ...
Страница 173: ...Appendix 8 5 Appendix 8 5 ...
Страница 174: ...Appendix 8 6 Appendix 8 6 ...
Страница 175: ...Appendix 8 7 Appendix 8 7 ...
Страница 176: ...Appendix 9 ...
Страница 178: ...Appendix 11 1 Appendix 11 1 ...
Страница 179: ...Appendix 11 2 Appendix 11 2 ...
Страница 180: ...Appendix 13 ...
Страница 181: ...Appendix 13 1 ...
Страница 182: ...Appendix 14 Appendix 14 ...
Страница 183: ...Appendix 15 1 Appendix 15 1 ...
Страница 186: ...Appendix 17 Appendix 17 ...
Страница 187: ...Appendix 18 ...
Страница 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Страница 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...