Charging Table
OD AMBIENT TEMP
(degF)
Subcooling
Weigh in
Weigh in
(degF)
Charge
Charge
< 65° F
65° F to 105° F
> 105° F
8° F ± 1° F
NOTE: Subcooling information is only valid while the unit is
operating at 100% capacity or 100% of compressor speed in
CHARGE MODE. Compressor speed is displayed under
STATUS menu in the thermostat.
8. For TXV Indoor Unit
The system subcooling should be 8°F ± 1°F (*1). If
not in that range, adjust subcooling and superheat
according to the following procedure.
a. If subcooling and superheat are low, adjust TXV
to 8°F ± 1°F superheat, then check subcooling.
NOTE: To adjust superheat, turn the valve stem
clockwise to increase and counter clockwise to
decrease.
b. If subcooling is low and superheat is 8°F ± 1°F,
add charge to rise subcooling to 8°F ± 1°F (*1),
then check superheat.
c. If subcooling is low and superheat is high, add
charge to rise subcooling to 8°F ± 1°F (*1), then
check superheat.
d. If subcooling is 8°F ± 1°F (*1) and superheat is
high, adjust the TXV valve to 8°F ± 1°F superheat,
then check subcooling.
e. If subcooling and superheat are high, adjust the
TXV valve to 8°F ± 1°F superheat, then check
subcooling.
f. If subcooling is high and superheat is 8°F ± 1°F,
remove charge to lower the subcooling to 8°F ±
1°F (*1), then check superheat.
g. If subcooling is high and superheat is low, adjust
the TXV valve to 8°F ± 1°F superheat and remove
charge to low the subcooling to 8°F ± 1°F (*1).
h. If subcooling is 8°F ± 1°F (*1) and superheat is
low, adjust the TXV valve to 8°F ± 1°F superheat
and remove charge to lower the subcooling 8°F ±
1°F (*1), then check the superheat.
NOTE: It is recommended to add charge in 4
oz. increments each time to achieve the target
subcooling.
C
HECK
THE
S
CHRADER
PORTS
FOR
LEAKS
AND
TIGHTEN
VALVE
CORES
,
IF
NECESSARY
. I
NSTALL
CAPS
FINGER
-
TIGHT
.
NOTICE
D
O
NOT
ADJUST
THE
CHARGE
BASED
ON
SUCTION
PRESSURE
UNLESS
THERE
IS
A
GROSS
UNDERCHARGE
.
NOTICE
SUCTION PRESSURE
PSIG
R-410A °F
LIQUID PRESSURE
PSIG
R-410A °F
50
1
200
70
52
3
210
73
54
4
220
76
56
6
225
78
58
7
235
80
60
8
245
83
62
10
255
85
64
11
265
88
66
13
275
90
68
14
285
92
70
15
295
95
72
16
305
97
74
17
325
101
76
19
355
108
78
20
375
112
80
21
405
118
85
24
415
119
90
26
425
121
95
29
435
123
100
31
445
125
110
36
475
130
120
41
500
134
130
45
525
138
140
49
550
142
150
53
575
145
160
56
600
149
170
60
625
152
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
ATTENTION INSTALLER - IMPORTANT NOTICE!
Please read carefully before installing this unit.
•
Do not attach any wires to the R & C Terminals on the
Heat Pump Unit, as they are not needed for inverter unit
setup.
•
Data Line Terminals #1 and #2 are polarity sensity. Only
the data lines, 1 and 2 are required between the indoor
and outdoor units.
•
Data Line Terminal #1 from outdoor unit must connect to
terminal #1 on indoor unit and data line terminal #2 from
outdoor unit must connect to terminal #2 on indoor unit.
Verify wires are not reversed.
•
Calculate the Liquid Line Set length and weigh in 0.6
ounces per foot of R410A refrigerant for any length
over 15 feet.
Or
•
Charge by Sub-cooling.
Sub-cooling should be 8°F ± 1°F. after adjusting charge,
please allow at least 20 minutes for the system to stabilize
before making further charge adjustment.
Содержание Amana VZC20
Страница 6: ...6...
Страница 48: ...48 4 Select YES to continue 5 Select HEAT PUMP 6 Select SYS SETUP...
Страница 55: ...55 NOTE BOOST MODE is applicable only for AVZC200 AB and GVZC20 AA or later revision...
Страница 56: ...56 https partnerlinkmarketing goodmanmfg com goodman info finder plus...
Страница 57: ...57 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 58: ...58 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 59: ...59 THIS PAGE IS INTENTIONALLY LEFT BLANK...