9.  Once satisfied with BOOST MODE adjustments, 

navigate to the HOME screen by selecting the Previous 

Menu button three times then selecting HOME.

Dehumidification 

The thermostat reads the indoor humidity level from the 

CTK04 and allows the user to set a dehumidification target 

based on these settings. The thermostat controls the 

humidity level of the conditioned space using the cooling 

system. Dehumidification is engaged whenever a cooling 

demand is present and structural humidity levels are above 

the target level. When this condition exists, the circulating 

fan output is reduced, increasing system run time, over 

cooling the evaporator coil and ultimately removing more 

humidity from the structure than if only in cooling mode. 

The CTK04 also allows for an additional overcooling limit 

setting from 0°F to 3°F setup through the Installer Option 

menu (directions following). This allows the cooling system 

to further reduce humidity by lowering the temperature up 

to 3°F below the cooling setpoint in an attempt to better 

achieve desired humidity levels.

By default, dehumidification needs to be turned ON at the 

thermostat via the Dehumidification Equipment menu. De

-

humidification  can  be  activated  at  the  original  equipment 

setup by selecting the A/C with Low Speed Fan button in 

the  Dehumidification  Menu. Availability  can  be  verified  by 

pressing MENU on the home screen. Scroll down and if a De-

humidification button is present, dehumidification is activated.
If Dehumidification is not available in the menu then it must 

be enabled through the Installer Options menu. Use the 

following procedure to enable and disable dehumidification:

1.  On the CTK04 HOME screen select MENU.

2.  From the MENU screen, scroll down and select Installer 

Options.

3.  Enter installer password if known. 

 

a.  The password is the thermostat date code and can 

be obtained by selecting the red Cancel button and 

selecting the Dealer Information button. 

 

b.  Once recorded, click the green OK button and 

return to the previous step.

4.  Select YES to continue.

5.  Select View / Edit Current Setup.

6.  Scroll down and select Dehumidification.

7.  Once open select Dehumidification Equipment: None.

8.  From the Dehumidification Menu select A/C with Low 

Speed Fan and click the green Done button.

9.  Additional Dehumidification operational options can be 

selected in the resulting window.

10. Once satisfied with the selection, navigate to the HOME 

screen by selecting the Done button and selecting Yes 

to verify the changes.

11. Select Previous Menu, then the HOME to return to the 

main menu.

Dehumidification Tips

For effective dehumidification operation:

•   Ensure “Dehum” is NOT set to “OFF” through the 

Installer Options menu and/or in the ComfortNet User 

Menu (COOL SETUP). 

-   If except OFF, the Dehumidification menu should  

    be visible in the main menu.

• 

  Verify the cooling airflow profile is set to “Profile D”. 

 

• 

See the Cool Set-up section of the Installation 

Manual for complete airflow profile details. 

 

• 

By default, “Dehum” is STD and the cooling airflow 

profile is set to “Profile D”.

• 

  For additional dehumidification control, airflow settings 

are field adjustable and can be fine-tuned to a value 

that is comfortable for the application from a range of 

Cool Airflow Trim. 

 

-   In addition, the system can have Enhanced 

Dehumidification operation in setting “A”, “B”, 

or “C” of “Dehum” based on dehumidification 

demand. 

 

-

See the “Dehumidification Select” section of the 

Installation Manual for more detail.

Содержание Amana VZC20

Страница 1: ...following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety info...

Страница 2: ...4 Refrigerant Lines 5 Leak Testing Nitrogen Or Nitrogen Traced 7 Electrical Connections 8 System Start Up Procedure 10 Coolcloud Hvac Phone Application 11 Comfortbridge System 13 Heat Pump Advanced F...

Страница 3: ...cing a condensing unit heat pump or air handler the system must be manufacturer approved and Air Conditioning Heating and Refrigeration Institute AHRI matched NOTE The installation of an inverter heat...

Страница 4: ...his unit on a roof structure ensure the roof structure can support the weight and that proper consideration is given to the weather tight integrity of the roof Since the unit can vibrate during operat...

Страница 5: ...through an area that may reach temperatures of 30 F or higher than ambient in cooling mode and or if the temperature inside the conditioned space may reach a temperature lower than ambient in heating...

Страница 6: ...6...

Страница 7: ...refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing Standing Pressu...

Страница 8: ...leak free proceed to system charging and startup 4 If pressure rises above 1000 microns but holds steady below 2000 microns non condensable air or moisture may remain or a small leak is present Retur...

Страница 9: ...see the production specification sheet or the unit serial plate must be provided for connection of the unit This circuit must be protected with the required safety devices When using residual current...

Страница 10: ...ER CAUTION ENSURE VALVES ARE OPEN AND ADDITIONAL CHARGE IS ADDED BEFORE APPLYING POWER CAUTION Type of Elbow Fittings 3 4 7 8 1 1 8 90 short radius 1 7 2 2 3 90 long radius 1 5 1 7 1 6 45 0 7 0 8 1 In...

Страница 11: ...re starting the CHARGE MODE turn off the Cool or Heat mode and electric heater or gas furnace a Inverter units are charged by any of the following methods setting the CR9 menu Charge Mode to ON throug...

Страница 12: ...subcooling 8 F 1 F 1 then check the superheat NOTE It is recommended to add charge in 4 oz increments each time to achieve the target subcooling CHECK THE SCHRADER PORTS FOR LEAKS AND TIGHTEN VALVE CO...

Страница 13: ...ification terminal Without this type of thermostat dehumidification operation does not work Dehumidification requires a thermostat capable of reading the indoor humidity level and allowing the user to...

Страница 14: ...on test is enabled from this menu which enables a functional check of the equipment in addition to ensuring proper stop valve position Cool Set up The system allows for the adjustment of several cooli...

Страница 15: ...an attempt to better achieve desired humidity levels When Dehumidification mode exists the circulating fan output is reduced increasing system run time over cooling the evaporator coil and ultimately...

Страница 16: ...ted and additional heating is not requested and additional heating is not required All other values mean defrost is being requested and additional heat is being requested DEHUMIDIFICATION REQUEST Requ...

Страница 17: ...ft above the indoor unit select INDOOR LOWER RESET FOR SYSTEM SET UP NO or YES Selecting yes will reset any system setting to their factory defaults SYSTEM VERIFICATION TEST OFF or ON System Verifica...

Страница 18: ...ompressor into defrost mode during an active heat pump heat call Ensure that the heat pump is operating in heat mode before enabling this option HEAT PUMP HEATING TRIM FACTOR HIGH 1 15 to 15 in 5 incr...

Страница 19: ...OR MOTOR HIGH LOW PRESSURE TRANSDUCER H LPT HIGH PRESSURE SWITCH HPS DS1 DS2 DIP SWITCH SEG1 SEG3 7 SEGMENT DISPLAY Z1C Z4C FERRITE CORE BS1 BS3 PUSH BUTTON SWITCH RVC REVERSING VALVE COIL M1C COMPRES...

Страница 20: ...RD RD BL U V W M1C BK RD YL M1F BK WH RD RD L2B L1B BK NOISE FILTER BOARD L2A L1A RD BK TRANSFORMER 208 240 V 3 1 2 24V L1C L2C TERMINAL BLOCK FIELD WIRING H LPT GND INVERTER BOARD COMPRESSOR TERMINA...

Страница 21: ...ICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIAT...

Страница 22: ...CITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATE...

Страница 23: ...X X X X X X X X X X ID suction temp is too high X X X X X ID suction temp is too low X X X Mixture of non condensible gas X X X X X X X X OD fan motor failure X X X X X X X RV failure X X X X X X X X...

Страница 24: ...too low X X X X X X X X X Mixture of non condensible gas X X X X X X X X X X OD fan motor failure X X X X X X X X X RV failure X X X X X X X X X RV coil failure X X X X X X X X X Over charge X X X X X...

Страница 25: ...w pressure faults Control has determined continued operation is acceptable This indicates they may be a problem with the equipment Stop valve not completely open Restriction in refrigerant lines Low r...

Страница 26: ...Repair replace if needed 32 E32 HI TEMP CTRL1 This error indicates the equipment is experiencing high temperature faults on the outdoor control board Ambient air conditions too high Cooling bracket sc...

Страница 27: ...ol has detected a voltage related issue with the compressor High or low voltage from supply The compressor wire is lost phase Faulty control board Correct low high line voltage condition Contact local...

Страница 28: ...n motor Replace if needed B9 Eb9 LOW ID AIRFLOW Estimated airflow from motor is lower than the airflow requirement Failed indoor blower motor Indoor fan motor not properly connected Too much static pr...

Страница 29: ...he LED status and the corresponding potential problem Green receive LED Indicates network traffic The table below indicates the LED status and the corresponding potential problem Learn button Used to...

Страница 30: ...corresponding Screen within the display itself which allows the user to navigate and use the features Example The Fault Code is accessed and displayed from Screen 0 of the 7 segment display The Fault...

Страница 31: ...shows the most recent fault To access hold the RECALL button for 5 seconds at screen 0 To access hold the RECALL button for 5 seconds at screen 1 To access hold the RECALL button To access hold the RE...

Страница 32: ...w the user to see the six most recent system faults For a list of the fault codes please see the TROUBLESHOOTING tables in this document 1 SCREEN 0 SCREEN 1 The display will change to SCREEN 1 Display...

Страница 33: ...etting Press RECALL Press RECALL Item number Display flickers at 1 second intervals Value MONITORING MODE NAVIGATION SCR This screen allows the user to monitor system variables as shown in the tables...

Страница 34: ...tem settings as shown in the tables at the end of this section SCREEN 0 Press RECALL Press RECALL to increase the value Press TEST to change setting Press RECALL Press TEST to complete setting and ret...

Страница 35: ...the number Press RECALL Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode Press RECALL Press RECALL Press RECALL SCREEN 0 OFF ON Blink interval 0 4 s...

Страница 36: ...0 Stop 1 Cooling Start up 2 Heating Start up 3 Oil Return Operation 4 Heating Operation 5 Defrost Operation 6 Cooling Operation 3 Compressor Reduction Mode 0 OFF 1 ON 4 demand unit Cut off the decima...

Страница 37: ...15 High cooling or hea ng NOTE Parameters as per factory se ng are highlighted in bold and underlined combina on trimmore there are restric ons on theposi to con rm the r ow Trim restric ons in the la...

Страница 38: ...ning of the outdoor coil becomes necessary hire a quali ed servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large los...

Страница 39: ...tdoor Unit Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING...

Страница 40: ...y sensitive Only the data lines 1 and 2 are required between the indoor and outdoor units Data line terminal 1 from outdoor unit must connect to terminal 1 on indoor unit and data line terminal 2 from...

Страница 41: ...section Before starting the SYSTEM TEST turn off the electric heater or gas furnace NOTICE Before starting the SYSTEM TEST turn off the electric heater or gas furnace 1 Ensure the thermostat is insta...

Страница 42: ...he password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 6 Select YES to continue 7 From the ComfortNet USER MENU selec...

Страница 43: ...to run for its duration 5 15 minutes EQUIP TEST SCREEN will show the system test is ON once selected System test will operate the outdoor unit and the indoor unit through a series of startup tests Pl...

Страница 44: ...odes to clear Set Thermostat to CHARGE MODE Please follow the following sequence to enter CHARGE MODE CHARGE mode allows for charging of the system System operates for a duration of approximately one...

Страница 45: ...ler password The password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 4 Select YES to continue 5 Select HEAT PUMP 6 Se...

Страница 46: ...mode If charging is not complete after 1 hour repeat 7 and 8 Refer to Adjust Refrigerant Level and Measure Subcooling to Verify Proper Charge for refrigerant charge level adjustment 9 To terminate CH...

Страница 47: ...le only for VZC200 1AB and GVZC20 AA or later revision BOOST MODE performance is most effective when paired with an electronic expansion valve enabled indoor unit BOOST MODE is ON by default and is ac...

Страница 48: ...48 4 Select YES to continue 5 Select HEAT PUMP 6 Select SYS SETUP...

Страница 49: ...turns BOOST MODE OFF or ON BOOST MODE is on by default 8 BOOST TEMP adjusts the activation temperature from 70 F to 105 F Always ON option is also available to permanently engage BOOST MODE Factory de...

Страница 50: ...able and disable dehumidification 1 On the CTK04 HOME screen select MENU 2 From the MENU screen scroll down and select Installer Options 3 Enter installer password if known a The password is the therm...

Страница 51: ...times Example A leak in the system low refrigerant charge or an incompletely open stop valve can cause the unit to flash error code E15 This error code suggests that the unit is experiencing operatio...

Страница 52: ...7 1 2 minutes The motor then steps up to the full demand airflow Profile D has a 1 2 minute at 50 airflow OFF delay OFF OFF Airflow Tables Dehumidification Select Dehumidification requires a thermost...

Страница 53: ...g Within the selected range choose the specific maximum compressor RPS for the system configuration Heat Set Up This menu allows for the adjustment of several heating perfor mance variables Heat Airfl...

Страница 54: ...nly for AVZC200 AB and GVZC20 AA or later revision ATPRM is shown in AVZC200 AA and GVZC20 AA revision Only for AVZC200 AB and GVZC20 AA or later revision PSD is shown in AVZC200 AA and GVZC20 AA revi...

Страница 55: ...55 NOTE BOOST MODE is applicable only for AVZC200 AB and GVZC20 AA or later revision...

Страница 56: ...56 https partnerlinkmarketing goodmanmfg com goodman info finder plus...

Страница 57: ...57 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 58: ...58 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 59: ...59 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 60: ...and Quebec residents to register their product does not diminish their warranty rights For Product Registration please register as follows Goodman Brand products https www goodmanmfg com product regis...

Отзывы: