26
Troubleshooting
ClimateTalk
Fault Code
PCB LED
Display
Transmitted ClimateTalk
Message
s
n
o
it
c
A
e
vi
t
c
e
rr
o
C
s
e
s
u
a
C
e
l
b
a
b
o
r
P
tl
u
a
F
t
a
t
s
o
m
r
e
h
T
22
E22
HI DISCH TEMP
This error indicates the equipment is
experiencing frequent high discharge
temperature faults.
Discharge thermistor is not put on
correct position.
Discharge thermistor inoperable or
improperly connected
Discharge thermistor is put on incorrect
position or off
Low refrigerant charge
Overcharge
Faulty compressor
Check discharge thermistor resistance and
connections; Repair/replace as needed
Check discharge thermistor position
Check refrigerant charge level; Adjust if needed
Check the compressor; Repair/replace if needed
23
E23
DISCH TEMP FAIL
The control has detected that the
Discharge Temperature Sensor is out of
range.
Discharge thermistor inoperable or
improperly connected
Check discharge thermistor resistance and
connections; Repair/replace as needed
24
E24
HPS OPEN
The high pressure switch is open.
High pressure switch (HPS) inoperable
Check resistance on HPS to verify operation; Replace
if needed
25
E25
AIR SENSOR FLT
The outdoor air temperature sensor is
open or shorted.
Faulty outdoor thermistor sensor or
disconnect
Inspect and test sensor; Replace sensor if needed
26
E26
PRESSURE SENSOR
The control determines that the pressure
sensor is not reacting properly.
Low pressure sensor inoperable or not
properly connected
Check the connection to low pressure sensor;
Repair/replace if needed
27
E27
COIL TEMP FAIL1
The control detects that the Outdoor
Defrost Sensor is out of range.
Outdoor defrost thermistor inoperable or not
properly connected
Check the connection to OD defrost thermistor; Repair
as needed
28
E28
COIL TEMP FAIL2
The control has detected that the Outdoor
Coil Temperature Sensor is out of range.
Outdoor coil thermistor inoperable or not
properly connected
Check the connection to OD coil thermistor;
Repair/replace if needed
29
E29
LIQ TEMP FAIL
The control has detected that the Liquid
Temperature Sensor is out of range.
Liquid thermistor inoperable or not properly
connected
Check the connection to liquid thermistor;
Repair/replace if needed
30
E30
OD CTRL FAIL3
Indicates the control board may need to
be replaced.
Wiring to control board disconnected
Faulty control board
Noise
Check wiring to control board; Repair as needed
Replace control board if necessary
31
E31
HI LEAK CURRENT
The control has detected high leakage
current (high voltege).
Improper ground
Faulty compressor
Check ground screws/lugs and wiring; Repair/replace
if needed
Check the compressor; Repair/replace if needed
32
E32
HI TEMP CTRL1
This error indicates the equipment is
experiencing high temperature faults on
the outdoor control board.
Ambient air conditions too high
Cooling bracket screw(s) missing or not
properly fastened (2-4 ton only)
No or poor thermal grease coating between
cooling plumbing and cooling bracket on control
board (2-4 ton only)
Outdoor fan low speed (5 ton only)
No flow or limited flow through control board
cooling circuit (potential restriction in line or low
refrigerant) (2-4 ton only)
Stop valve not completely open (2-4 ton only)
Cycle power; re-try during usable ambient temperature
range
Verify cooling bracket screws in place and secure;
Secure fasteners as needed (2-4 ton only)
Check thermal grease inside cooling bracket on control
board; Apply additional grease as needed
Check outdoor fan motor & wiring; Repair/replace if
needed (5 ton only)
Check for restriction in line
Check refrigerant charge level; Adjust if needed (2-4
ton only)
Check the opening of stop valve, should be full open;
Repair/replace if needed (2-4 ton only)
33
-
HI TEMP CTRL2
This error indicates the equipment is
experiencing high temperature faults on
the outdoor control board. Control has
determined continued operation is
acceptable. This indicates they may be a
problem with the equipment.
Ambient air conditions too high
Cooling bracket screw(s) missing or not
properly fastened (2-4 ton only)
No or poor thermal grease coating between
cooling plumbing and cooling bracket on control
board (2-4 ton only)
Outdoor fan low speed (5 ton only)
No flow or limited flow through control board
cooling circuit (potential restriction in line or low
refrigerant) (2-4 ton only)
Stop valve not completely open (2-4 ton only)
Cycle power; re-try during usable ambient temperature
range
Verify cooling bracket screws are in place and secure;
Secure fasteners as needed (2-4 ton only)
Check thermal grease inside cooling bracket on control
board; Apply additional grease as needed
Check outdoor fan motor & wiring; Repair/replace if
needed (5 ton only)
Check for restriction in line
Check refrigerant charge level; Adjust if needed (2-4
ton only)
Check the opening of stop valve - it should be fully
open; Repair/replace if needed (2-4 ton only)
34
E34
CURRENT SPIKE
Board detected a high current condition.
This indicates the potential for a short
circuit.
Current spike in supply
Stop valve not completely open
The compressor wire is lost phase
Faulty control board
Faulty compressor
Check power supply for in-rush current during start-up
or steady state operation
Check the opening of stop valve, should be full open;
Repair/replace if needed
Check the wire between control board and compressor
Replace control board if necessary
Check the compressor; Repair/replace if needed
(*1) This message is displayed when using the CTK04 thermostat
Содержание Amana VZC20
Страница 6: ...6...
Страница 48: ...48 4 Select YES to continue 5 Select HEAT PUMP 6 Select SYS SETUP...
Страница 55: ...55 NOTE BOOST MODE is applicable only for AVZC200 AB and GVZC20 AA or later revision...
Страница 56: ...56 https partnerlinkmarketing goodmanmfg com goodman info finder plus...
Страница 57: ...57 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 58: ...58 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 59: ...59 THIS PAGE IS INTENTIONALLY LEFT BLANK...