Hi-T2
Centralised controller
42
12 Winter temperature consent
Sets the threshold above which winter season is
considered (Water outlet temperature)
0.0
50.0
35.0
°C
13 Summer temperature consent
Sets the threshold above which summer season is
considered (Water outlet temperature)
0.0
25.0
25.0
°C
14 Antifreeze setting
Winter antifreeze temperature
0.0
10.0
4.0
°C
15 Auxiliary output deviation
Sets the temperature difference value with respect to the
setpoint for auxiliary output activation
0.0
10.0
0.5
°C
17 Destratification time off
0
60
15
min
18 Destratification time on
0
10
0
min
19 Fan activation delay in winter after hot valve
0
250
60
sec
20 Fan activation delay in winter with respect to activation of
primary heater output.
0
250
60
sec
21 Post-ventilation
Fan deactivation delay in Winter operation when the primary
electric heater is deactivated
0
250
60
sec
22 Fan motor control mode
1 = Remote function from master with possible action by user
2 = Absolute function only by Master
3 = funzionality as 1 if the Zone is ON, otherwise constrainded
OFF
1
3
2
---
23 Fan coil ID offset
Extends the possibility of having network addresses > 22
elements
Address = (Par23 * 32) + Dip-Switch value
You need to restart the RFC control in order to use the new
address
0
2
0
---
To change the value of a parameter:
•
having entered the parameter list of the chiller, fan coil or keyboard, use the up and down arrow keys to scroll through the
pages of the parameters, up to the desired parameter;
•
press on the currently set value;
•
the current value turns red to indicate that it can be changed by using the up and down arrows;
•
select the desired value and press the confirmation tick .
Note
: after selecting the desired value, if you miss the confirmation tick, the previous setting value will be kept.
To copy the value of a parameter to all fan coils:
By pressing the "COPY"
near the set value, this last one will be copied automatically to all present fan coils.
9
DESCRIPTION OF RFC SYSTEM
First of all refer to the specific RFC manual (MCO01137I0300 FAN COIL REGULATOR).
The RFC system can be installed with the hydronic terminals of the VE, HCN and HCNA series.
There are two ways to install the RFC control system:
1)
Installation inside fan coil compartment
2)
Wall installation using screws
In the standard configuration, the Hi-T2 control panel allows a complete control of the fan coil units; however with a switchable
configuration of the RFC control system, you can get access to some manual features for comfort adjustment. In fact, it is possible
to adjust the setpoint using the main knob giving a slight variation of the setpoint value (up to +/-5°C) that is already set by the Hi-
T2 control panel. Moreover, with appropriate parameterization, you can allow the RFC control system to operate manually on
ventilation; particularly, it is possible to establish whether to keep the automatic regulation made by the Hi-T2 control panel, or to
use the appropriate knob whether to stop or set one of the 3 fan speeds.