Hi-T2
Centralised controller
21
2.
enter the “
Service menu
”
;
3.
enter the service password and press on the confirmation tick.
4.
Enter in “
Network scanning
”;
5.
press the confirmation tick near the word "
Start:
" and wait the system to scan the network;
6.
at the end of scanning phase, the system should find all the chillers (max 7 in cascade) and all the fan coil units of the same
network. If the number of fan coils found does not match those installed, then the wiring is not done correctly.
If one or more fan coils that were correctly addressed and detected disconnect from the network (for example in case of
fan coil power failure), the centralised keyboard proceeds with updating the number of fan coils actually in operation in the
system with a delay of 2 minutes from the occurrence of the failure, displaying an Error message after the update. When
the disconnected fan coils are reconnected, the centralised keyboard recognises them automatically, preserving the
previous settings.
4.4.3
ASSIGNMENT OF THE FAN COILS TO THE ZONES AND ZONE NAME CUSTOMISATION
To associate the fan coils to the desired zones, it is necessary to follow the procedure below:
1.
enter the "
Configuration
" page and from there in the "
Service Menu
" following the same procedure as in Paragraph 4.4.1 (points 2-4) and
select "
Zone configuration
";
2.
press “
Zone 1
”;
3.
press on the second line where the actual name "
Zone 1
" appears and change the name of the zone using the keyboard which appears
on the screen (you can enter a maximum of 9 characters);
4.
to confirm the new name press
"Enter
", otherwise press "
Esc
";
5.
press on the value that appears near the wording "
From
" (the value is highlighted in red);
6.
use the arrows keys to select the address of the first fan coil of the zone that you are configuring;
7.
press the confirmation tick;
8.
press on the value that appears near the wording "
To
" (the value is highlighted in red);
9.
use the arrows keys to select the address of the last fan coil of the zone that you are configuring;
10.
press the confirmation tick;
11.
repeat the operations from number 2 to number 10, applying the same procedure to the other zones that you want to configure.
4.5
SOLAR MANAGEMENT
This function is not totally configurable by the Hi-T2 controller. It is necessary to act directly on the chiller/heat pump controller by
setting the parameters H85 at 39, H86 at 38 and H103 at 30. The enabling is definitive by configuring the parameter S01 at 1 and
configuring the relative S parameters also by means of the Hi-T2 remote controller.
4.6
OPERATION OF CONNECTED UNITS
4.6.1
SWITCHING ON/OFF
When the zones have been configured and the fan coils associated, you may proceed with the “first start-up” of the connected
units. With just one touch, you may switch on or off the entire system from the single Hi-T2 keyboard or switch on the chillers and
manage the zones individually.
To operate the entire system:
from the main page of the system, go to "
Status setup”
;
1.
the following are listed in the menu: SYSTEM, CHILLER, ZONE -th.
2.
Press "
System
" and with a single operation, you can turn on or off all the fan coil units of all zones that are connected to the
remote control panel Hi-T2 and all chillers of the same plant:
WINTER
SYSTEM
SUMMER
OFF
PROGRAMMED
MANUAL
MANUAL ECO
OFF
PROGRAMMED
MANUAL
MANUAL ECO