Hi-T2
Centralised controller
14
•
Automatic adjustment (auto-mode)
To set the speed, use the up and down arrows, and then press the green button to confirm the selected speed.
3.4.2.1
BAR AREA OF FAN COIL FUNCTIONS
In the left side scroll bar, there are icons indicating the active functions or that can be activated in the concerned fan coil. In
particular:
Coloured icon = function enabled,
Faded icon = function configured on unit but not currently active.
Below there is a table with icons that may appear in the side scroll bar.
The presence/absence of the icon in the sidebar depends on whether the function referred to on the fan coil is enabled or disabled.
ORDER OF APPEARANCE
ICON
FUNCTION
1
WINDOW CONTACT
2
DOUBLE SET-POINT
3
HUMIDITY CONTROL
Table 2. Order of appearance of the icons in the fan coils function bar.
3.4.3
AREA Hi-T2
Pressing on the sensitive area
6
of Figure 5, you have access to a screen showing the version and the date of release of the firmware
installed.
3.4.4
ETHERNET CONNECTION CONFIGURATION
Pressing on the sensitive area
7
of Figure 5, the following page appears:
Figure 14. Ethernet configuration page
On this page there are the addresses for the configuration of an Ethernet connection. There is a parameter to also sign the
connection port (parameter 65, default port 80).
Logging in with service/manufacturer permission, you can change the default addresses.
A local web server is implemented to access the Hi-T2 from local area network with an HTML 4.01 compatible browser (see
Paragraph 5.2).
ETHERNET CONFIGURATION
IP Address
Subnet mask
Gateway
MAC