i-SHWAK V4 

Inverter air/water chillers and heat pumps with wall-mounted indoor unit and remote condensing outdoor unit 

26 

 

 

Terminal block Auxiliary Board 

 AB 

 Indoor unit 

Jumper 

Terminal 

Description 

CN3 

HP+ 

N.U. 

HP- 

N.U. 

LP+ 

N.U. 

LP- 

N.U. 

DT 

DHW terminals 

CN4 

PWM 1 / 0-10V 1 

Analog output for DHW circulator signal 

CN5 

PWM 2 / 0-10V 2 

Analog output for plant circulator signal 

CN7 

12V 

See 12V terminals 

AI10 

Ratiometric 0-10V analog input 

+5V 

Power supply for ratiometric 

CN8 

AI1 

IMP terminals 

AI2 

Outlet (flow) temp. sensor 

AI3 

Inlet temp. sensor 

AI4 

DHW secondary flow sensor 

CN9 

AD1 

DHW primay flow sensor 

AD2 

DHW seconday inlet temperature sensor 

DI1 

Flowswitch 

DI2 

ON/OFF terminals 

DI3 

SW termninals 

CN10 

Single-phase 230Vac 

NU 

DO1 

DO1 terminal 

DO2 

DO2 terminal 

DO3 

DO3 terminal 

DO4 

DO4 terminal 

DO5 

Phase 230Vac 

DO5 

DO5 terminal 

CN12 

NC1 

Normally Closed Changeover Contact 

C1 

Phase 230Vac 

NO1 

Normally Open Changeover Contact 

I+ / I- 

I+ / I- terminals 

GND 

GNDR terminal 

R+ / R- 

R+ / R- terminals 

E+ / E- 

E+ / E- terminals 

CN14 

NC2 

NC2 terminal 

C2 

Phase 230Vac 

NO2 

NO2 terminal 

For connecting the I- / I+ and GNDR terminals, 

t’s recommend to use a shielded twisted

-pair multipolar cable 5x0.75mm

2

8.7.2

 

Outdoor unit 

The  connections  listed  below  are  standard.  Other  connections  are  shown  in  the  manual  MCO  (Control  Manual)  of  the  control 
panel of the machine i-SHWAK V4. 

x

 

Remove the mounting screws of the cover of the power supply (see the paragraph 8.4.2.3.) 

x

 

Connect the cable to the terminals inside the electric box. 

x

 

For electrical connections please refer to the wiring diagrams given in the supplied MSE manual. 

8.7.2.1

 

Terminal block connections 

The terminal block must be connected in compliance with the following notes (the schema is only for illustration). 

 

Outdoor unit terminal block 

Terminal 

Description 

GND 

Grounding 

N1 

Neutral 

L1 

Phase 1 

L2 

Phase 2 (only for three-phase systems) 

L3 

Phase 3 (only for three-phase systems) 

NO 

Power supply (230V AC) general alarm (closed if the alarms is on) 

Neutral 

NC 

Power supply (230V AC) general alarm (closed if the alarm is off) 

I+ / I- 

Modbus Slave 

Wiring with indoor unit 

R+ / R- 

Modbus Master 

Wiring with indoor unit 

GNDR 

GND reference signals 

(Modbus reference mass for connection with indoor unit)

 

 

Содержание ADVANTIX i-SHWAK V4 06

Страница 1: ...ssue i SHWAK V4 06 16 T 10 2017 Catalogo Catalogue Katalog Brochure Sostituisce Superseedes Ersetzt Remplace MUI01110H7920 01 02 2017 INVERTER AIR WATER CHILLERS AND HEAT PUMPS WITH WALL MOUNTED INDOO...

Страница 2: ...ATER CHILLERS AND HEAT PUMPS WITH WALL MOUNTED INDOOR UNIT AND REMOTE CONDENSING OUTDOOR UNIT Possible wasted electrical or electronic devices products should not be located together with normal domes...

Страница 3: ...facture UNI EN 378 1 UNI EN378 2 UNI EN 12735 1 Norme armonizzate applicate alla progettazione ed alla costruzione UNI EN 378 1 UNI EN378 2 UNI EN 12735 1 3 Others European Directives and harmonized s...

Страница 4: ...1 GENERALITY 14 8 2 LIFTING AND HANDLING 15 8 2 1 Indoor unit 15 8 2 2 Outdoor unit 15 8 3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 16 8 3 1 Indoor unit 16 8 3 2 Outdoor unit 16 8 4 HYDRAULIC CONNECT...

Страница 5: ...9 OPERATION LIMITS 38 19 1 EVAPORATOR WATER FLOW RATE 38 19 2 CHILLED WATER PRODUCTION SUMMER OPERATION 38 19 3 HOT WATER PRODUCTION WINTER OPERATION 38 19 4 AMBIENT AIR TEMPERATURE 38 20 CORRECTION F...

Страница 6: ...ny updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give infor...

Страница 7: ...arts of the equipment without the specific consent of the manufacturer The manufacturer shall have no responsibility whatsoever in case of unauthorised operations Using components expendable materials...

Страница 8: ...safety requirements currently in force In case of slippery floors users have to wear safety shoes with non slip soles Gloves During maintenance or cleaning operation protection gloves have to be used...

Страница 9: ...TROL PERSONAL PROTECTION Control parameters AEL 8 h e 12 h TWA 1000 ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained...

Страница 10: ...fitted mod RExxxx 3 Mixer s controller logic for plant side in both heating and cooling operations controller logic for solar integration Controller logic for relaunching circulator secondary plant s...

Страница 11: ...parate chamber in order to be separated from the air flow for reducing noises and are also supplied with crankcase heater which operates in order to avoid the oil dilution which may cause seizure of t...

Страница 12: ...water pipe line from the plant operating and antifreeze sensor installed at the outlet pipe of the water to the plant and on water side a water flow switch is installed to protect the evaporator All i...

Страница 13: ...fixed digits equals to 0 if are not used 9 no 2 variable digits field MC which identifies the i SHWAK V4 series in its customizations the field MC is composed of two digits 0110917 CT AE K3V ACS GI RE...

Страница 14: ...IELDS VARIANTS shown above Indoor unit Model Description CT AE ACS Selectable accessories V4 06 MP1 Single phase wall mounted unit 16 0 0 K3V GI RE MPR1 Single phase wall mounted unit with rapid produ...

Страница 15: ...to take any possible precautions Not observing the rules reported on this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in...

Страница 16: ...erwise take special care not to damage the unit when handling it Removal of the packing box x Cut the strap fasteners x Open the top part x Remove the apparatus from the packing box x Remove the clear...

Страница 17: ...is avoided in order to allow the air recirculation It is advisable to create a proper basement with a size similar to unit foot print Unit vibration level is very low it is advisable however to fit a...

Страница 18: ...itional expansion vessel For the installation position of the expansion vessel indicated as additional expansion vessel please refer to Paragraph 8 5 WARNING check that the weight of the pipes does no...

Страница 19: ...Liquid line see Paragraph 14 3 F Ingresso alimentazione elettrica G Discharge of safety valve hose connector 14 mm H Water supply inlet 3 4 M I To the DHW R use 3 4 M J From the puffer ACS R 3 4 M K...

Страница 20: ...ect a rubber pipe to the connection disposed on the unit see connection positions Secure it with pipe clamp Direct the hose towards an appropriate location for unloading A sufficient slope should be m...

Страница 21: ...xpansion vessel not supplied OUTDOOR UNIT Piping connection for gas and liquid shall be done by the installer KEY Filter with extractables cartridge Charging unit with pressure reduccer device Dischar...

Страница 22: ...It is necessary to install one automatic air vent at the highest point of the plant circuit WARNING It is recommended to install a 3 bar relief valve not supplied as shown in the plant diagram It is n...

Страница 23: ...ds of the roll and cut pipe The equipment does not require any preloaded refrigerant lines The refrigerant pipes should be straight as possible and the necessary bends must have radius more than 300mm...

Страница 24: ...the technical characteristics see the chapter 14 WARNING The supply voltage s fluctuations cannot exceed 10 of the nominal value If this tolerance should not be respected please contact our technical...

Страница 25: ...f the electrical panel x Connect the cable to the terminals inside the electric box x For electrical connections please refer to the manuals of wiring diagrams A Power cable inlet B Auxiliary connecti...

Страница 26: ...lation D02 Phase conductor for DHW valve 230Vac D02N Neutral conductor for DHW valve D03 Phase conductor for auxiliary plant system electric heater 230Vac DO3N Neutral conductor for plant system auxil...

Страница 27: ...C2 NC2 terminal C2 Phase 230Vac NO2 NO2 terminal For connecting the I I and GNDR terminals t s recommend to use a shielded twisted pair multipolar cable 5x0 75mm 2 8 7 2 Outdoor unit The connections l...

Страница 28: ...tric box then proceed to connect wire to the terminal block 3 Insert the cables PG cable glands located on the side of the unit to take them outside the unit 4 Close the electric box and the top panel...

Страница 29: ...event severe damages to compressors WARNING For the first installation and start up of the unit make sure that the unit is working correctly in both cooling and heating modes 10 INDICATIONS FOR THE US...

Страница 30: ...there is a possible oil leakage from compressor outdoor unit x Check if there is a possible water leakage from the hydraulic circuit indoor unit x Check the proper working of the flow switches outdoo...

Страница 31: ...p 35 C 55 C Classe A A A A A A PERFORMANCE DATA Unit Model i SHWAK V4 12 14 14T 16 16T Cooling Cooling capacity 1 min nom max kW 5 4 11 9 13 1 6 7 13 8 15 2 8 70 15 69 16 30 Input power 1 kW 2 65 2 93...

Страница 32: ...n motor Type DC Brushless Motor DC Brushless Motor Number 2 2 Refrigerant Type R410A R410A Refrigerant quantity 7 kg 4 9 5 1 Equivalent amout of CO2 ton 10 2 10 6 Design pressure high low MPa 4 2 2 7...

Страница 33: ...140 Max input power kW 0 140 0 140 Max input current A 1 05 1 05 Energy Efficiency Index EEI 0 23 0 23 Hydraulic circuit Expansion vessel of technical plant side L 8 8 Hydraulic plant flow return con...

Страница 34: ...A 230V 1 50Hz MP3 14 16 0 15 kW 1 07 A ND 2 15 kW 3 96 A 3 15 kW 5 40 A 4 65 kW 7 57 A 400V 3P N T 50Hz MPR1 06 08 0 13 kW 1 06 A 1 39 kW 6 54 A 2 13 kW 9 75 A 3 13 kW 14 10 A 4 63 kW 20 62 A 230V 1...

Страница 35: ...air water chillers and heat pumps with wall mounted indoor unit and remote condensing outdoor unit 34 Here also the range of the available head pressures that the unit can provide during the circulato...

Страница 36: ...SSURE DROP CURVE VDIS1 optional kit The characteristic curve corresponding to the Head pressure versus Water flow rate of the three way diverter valve only if the optional VDIS1 kit is present whose v...

Страница 37: ...optional electric heater is indicated with red dashed lines WARNING It is necessary to install on the DHW line between the instantaneous preparer and the mixers of domestic hot water of an anti scald...

Страница 38: ...i SHWAK V4 Inverter air water chillers and heat pumps with wall mounted indoor unit and remote condensing outdoor unit 37 T _Set_DHW 45 C T _Set_DHW 50 C...

Страница 39: ...r operation The allowed minimum temperature at the evaporator s outlet is 5 C for lower temperatures the unit should undergo some necessaries structural modifications and different setting parameters...

Страница 40: ...e hydraulic circuit Glycol Freezing point C CCF IPCF WFCF PDCF 10 3 2 0 985 1 1 02 1 08 20 7 8 0 98 0 99 1 05 1 12 30 14 1 0 97 0 98 1 10 1 22 40 22 3 0 965 0 97 1 14 1 25 50 33 8 0 955 0 965 1 2 1 33...

Страница 41: ...1 INDOOR UNITS 21 1 1 Indoor unit model MP DIMENSIONS mm MODELS A B C D E F G H I J K L M N O MP 37 92 147 162 71 277 140 172 205 237 269 314 43 893 343 21 1 1 Indoor unit model MPR DIMENSIONS mm MODE...

Страница 42: ...ter air water chillers and heat pumps with wall mounted indoor unit and remote condensing outdoor unit 41 21 2 OUTDOOR UNITS 21 2 1 MOD i SHWAK V4 06 08 21 2 2MOD i SHWAK V4 10 12 21 2 3 MOD i SHWAK V...

Страница 43: ...he screws number 2 3 4 of the user interface cover plate and the screw 1 from the side panel for separating the side panel from the front panel Detail A 3 Sequentially twist off the screws number 5 6...

Страница 44: ...oking tab on the basement indicated as C in the detail B and remove it 22 2 3 Mod i SHWAK V4 14 14T 16 16T 1 Remove the cover twisting off the screws number 1 2 3 4 5 6 7 8 9 2 Twist off the screws nu...

Страница 45: ...14 Electric heater optional 23 2 MPR MODEL INDOOR UNIT 1 Expansion vessel 2 Automatic air vent valve 3 Safety flow switch 4 Plate heat exchange 5 Plate heat exchange DHW R 6 Flowmeter DHW R 7 Circula...

Страница 46: ...brush it carefully it under running water 4 Place the metallic mesh filter cartridges in its position 5 Screw the plug filter 6 Charge the unit is described in the Paragraph 8 4 5 24 2 REPLACEMENT OF...

Страница 47: ...pansion board terminal block for GI2_ SL2 module Present only with RExxxx optional electric heater kit Present only with GI2 optional module 26 CONTROL LOGICS For the control logic please refer to the...

Страница 48: ...9 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa it e mail info advantixspa it A I R C O N D I T I O N I N G The data indicated in this manual is purely indicative The ma nufacturer reserves the...

Отзывы: