ME30 infobox connect
20
infobox connect
14. Signalling function S03
In SO3 mode the Delete button assumes a special role. It is connected to an external "Reset”
signal. If the reset signal is present, pressing the Delete button switches off the display
elements. If there is no reset signal, then pressing the Delete button switches the LEDs to a
steady light.
Message/pushbutton state
Indicator state
Int./ext.
Group message
Messages Pushb. operation
1st ind.
2nd ind.
horns
static
ackn.
dynam.
None
Not required
Off
Off
Off
Off
Off
Off
1st mess.
Not required
Fast
Off
On
On
On
On
arriving
flashing
2nd mess.
Not required
Fast
Fast
On
On
On
Off/On
arriving
flashing
flashing
Pending
Horn ackn.
Fast
Fast
Off
On
On
On
flashing
flashing
Pending
Message ackn.
Fast
Fast
Off
On
Off
On
flashing
flashing
Going
Not required
Fast
Fast
Off
Off
Off
Off
flashing
flashing
Gone
Delete/Reset
Steady light Steady light
Off
Off
Off
Off
disabled
Gone
Reset enabled
Off
Off
Off
Off
Off
Off
Pending
Horn ackn.
Fast
Fast
Off
On
On
On
flashing
flashing
Going
Not required
Fast
Fast
Off
Off
On
Off
flashing
flashing
Gone
Message ackn.
Fast
Fast
Off
Off
Off
Off
flashing
flashing
Gone
Delete/Reset
Steady light Steady light
Off
Off
Off
Off
disabled
Gone
Reset enabled
Off
Off
Off
Off
Off
Off