2. First-up indication: Single flashing light for alarms acc. to DIN 19235
Acoustic (internal and external horn) and visual indication (fast-flashing signalling LED) of the
first pending alarm message. All subsequent alarm messages are indicated by a steady light.
Upon acknowledgement of all messages the function starts again.
Message/pushbutton state
Indicator state
Int./ext.
Group message
Messages Pushb. operation
1st ind.
2nd ind.
horns
static
ackn.
dynam.
None
Not required
Off
Off
Off
Off
Off
Off
1st mess.
Not required
Fast
Off
On
On
On
On
arriving
flashing
2nd mess.
Not required
Fast
Steady light
On
On
On
Off/On
arriving
flashing
Pending
Horn ackn.
Fast
Steady light
Off
On
On
On
flashing
Pending
Message ackn.
Steady light Steady light
Off
On
Off
On
Going
Not required
Off
Off
Off
Off
Off
Off
Pending
Horn ackn.
Fast
Steady light
Off
On
On
On
flashing
Going
Not required
Fast
Steady light
Off
Off
On
Off
flashing
Gone
Message ackn.
Off
Off
Off
Off
Off
Off
3. New value indication: Single flashing light for alarms acc. to DIN 19235
Acoustic and visual indication of all alarm messages.
Message/pushbutton state
Indicator state
Int./ext.
Group message
Messages Pushb. operation
1st ind.
2nd ind.
horns
static
ackn.
dynam.
None
Not required
Off
Off
Off
Off
Off
Off
1st mess.
Not required
Fast
Off
On
On
On
On
arriving
flashing
2nd mess.
Not required
Fast
Fast
On
On
On
Off/On
arriving
flashing
flashing
Pending
Horn ackn.
Fast
Fast
Off
On
On
On
flashing
flashing
Pending
Message ackn.
Steady light Steady light
Off
On
Off
On
Going
Not required
Off
Off
Off
Off
Off
Off
Pending
Horn ackn.
Fast
Fast
Off
On
On
On
flashing
flashing
Going
Not required
Fast
Fast
Off
Off
On
Off
flashing
flashing
Gone
Message ackn.
Off
Off
Off
Off
Off
Off