2.3
Output
Control Type
Control Type
On/Off, P, PI, Auto tune PID, Valve Position Control
(without Feedback)
Manual Offset
±50% of P band
Proportional Band
0.1 to 200.0 %
Integral Time
0(off) to 1000 Sec
Derivative Time
0(off) to 250 Sec
Cycle Time
For SSR
For Relay
1 to 60 Sec
10 to 250 Sec (Hyst in on/off mode)
Relay Output (RL1, RL2)
Function
Control, Alarm
Type
Single Change over Three Terminals (C, NO, NC)
Rating
5A @ 230VAC / 30VDC
Relay Output (RL3, RL4)
Function
Alarm
Type
Single Change over Three Terminals (C, NO,)
Rating
5A @ 230VAC / 30VDC
SSR Output (Option in lieu of RL1)
Function
Control
Rating
11 VDC @ 20mA
Analog Output 1-AO1 (Option)
Function
Control, Retransmission
Current
0-20mA/ 4-
20mA @500Ω Max
Voltage
0-5V/ 1-5V/ 0-
10V @3 KΩ Min
Output accuracy
±0.25% of span
Analog Output 2-AO2 (Option)
Function
Retransmission
Current
0-20mA/ 4-
20mA @500Ω Max
Voltage
0-5V/ 1-5V/ 0-
10V @3 KΩ Min
Output accuracy
±0.25% of span
Communication Output-RS485 (Option)
Function
Read/Write all Parameters
Protocol
Modbus RTU
Baud Rate
9600, 19200, 38400
Transmitter supply
24V DC (±10%) @26mA (Current limited)