Model: TC5396
masibus
Doc. Ref. no. : - m105/om/101
Issue no. 00
User’s Manual
Page 36 of 40
51
Control output type
40051
Int
R + W
52
Control type
40052
Int
R + W
53
Control Output Low Limit
40053
Int
R + W
54
Control Output High Limit
40054
Int
R + W
55
Retransmission o/p Type -1
40055
Int
R + W
56
Retransmission o/p direction
–
1
40056
Int
R + W
57
Retransmission o/p Type -2
40057
Int
R + W
58
Retransmission o/p direction
–
2
40058
Int
R + W
59
Serial Number
40059
Int
R + W
60
Baud Rate
40060
Int
R + W
61
Function Key
40061
Int
R + W
62
Motor Travel time
40062
Int
R + W
63
Dead Band
40063
Int
R + W
64
Soak (Run/Stop)
40064
Int
R + W
65
Pass word
40065
Int
R + W
66
Version
40066
Int
R
10.3 Exceptional Response
TABLE– 8
CODE
MEANING
01
Function code Invalid. It must be 01, 05, 03 or 06.The function code received in the query is
not allowable action for the slave.
02
Illegal address value. The data address received in the query is not an allowable address for the
salve.
03
Illegal data value. A value contained in the query data field is not an allowable value for the
salve.
06
When Master device write some parameters to Slave device, If slave device busy
then it will send 06 code to indicate slave device is busy.
Note:
1.
Table the value & Range of each
Parameter.
EX: Input Type (Applicable Range: 0 to 8):
Input Type
Value
E-tc
0
J-tc
1
K-tc
2
T-tc
3
B-tc
4
R-tc
5
S-tc
6
RTD
7
0
–
10V
8