6.7 LEVEL 5 OUTPUT MODE
A3DY
(
a3dy
)
Alarm 3
Delay
Alarm Delay is amount of time (in sec), that
Relay-3 will wait before getting ON after the
alarm condition occurs.
1 to 99 sec
1
Output Type
is LIN(Linear)
45
A4TP
(
a4tp
)
Alarm Type
–
4
6
(
PV.A.L.))
Output Type
is not VPFN
46
A4HY
(
a4Hy
)
Alarm 4
Hysteresis
Set Hysteresis(in °C) for Alarm-4
1
Output Type
is not VPFN
47
A4LC
(
a4lC
)
Alarm 4 Logic
Set Logic for Alarm-4
norm
/
flsf
0 : NORM (Normal)
1 : FLSF (Fail-Safe)
0
(Normal)
Output Type
is not VPFN
48
A4DY
(
a4Dy
)
Alarm 4
Delay
Alarm Delay is amount of time (in sec), that
Relay-4 will wait before getting ON after the
alarm condition occurs.
1 to 99 sec
1
Output Type
is not VPFN
49
OUTPUT PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if
Only
Reg.
No.
Symbol
Name
COP
(
Cop
)
Control
Output Type
Select Controlling Type for Output
PiD
/
ONOF
2 : PID
3: ON-OFF
2
(PID
Type)
Control
output type
is PID
50
OT
(
ot
)
Output Type
Output Type
rely
/
ssr
/
lin
0 : RELY (Relay)
1 : SSR (Voltage Pulse Output)
2 : LIN (Linear)
3 : VPFN (Motor position control without slide
wire feedback)
Device can support RELAY or SSR output once
at a time. (Factory Settable)
** Device can support Control output type
PID
or
onoF.
(Factory Settable)
0
(Relay)
**VPFN, LIN
and SSR
option will
not appear if
COP(Control
Type) is ON-
OFF
51
COLO
(
CoLo
)
Control
Output Low
Limit in %
Control Output Low Limit in %.
0.0 to 100.0 %
(It will be always less then CO.HI)
0 .0
Control
output type
is PID
52
COHI
(
CoHi
)
Control
Output High
Limit in %
Control Output High Limit in %.
0.0 to 100.0 %
(It will be always greater then CO.LO)
1 0 0 .0
Control
output type
is PID
53