8. ALARM OUTPUT
For all Alarm outputs there are five settings. (As shown in configuration mode Menu)
Set Value (in run mode)
Type
Hysteresis(Dead band)
Direction (Normal/Fail safe)
Delay
SET VALUE: Alarm set point
8.1 ALARM TYPES
Various alarm operations are shown in the reference figure.
ALARM
TYPE
NO
Display
message
ALARM TYPE
Note
0
none
None
NO operation available
1
PvdH
Deviation High alarm
Ref figure 3
2
Pvdl
Deviation Low alarm
Ref figure 4
3
Pvdr
Deviation High & Low range alarm
Ref figure 5
4
Pvdb
Deviation High & Low Band alarm
Ref figure 6
5
PvaH
Absolute value High alarm
Ref figure 1
6
PvAL
Absolute value Low alarm
Ref figure 2
7
SPAH
Absolute value set point high alarm
Ref figure 7
8
SPAL
Absolute value set point low alarm
Ref figure 8
9
PSdH
Deviation High alarm with standby
Same as figure 3
10
PSdL
Deviation Low alarm with standby
Same as figure 4
11
PSdr
Deviation High & Low range alarm with standby Same as figure 5
12
PSdb
Deviation High & Low limit alarm with standby
Same as figure 6
13
PSAH
Absolute value High alarm with standby
Same as figure 1
14
PSAL
Absolute value Low alarm with standby
Same as figure 2
15
PV-E
PV error(OPEN/OVER/UNDER)
Note 1
NOTE-1:
The fault diagnosis output turns on in case of input burnout (PV) failure.